| Date |
Text |
| 2016-12-09 07:34:11 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC, 5TH EDITION (2014). |
| | |
| | 1- PLANS SUBMITTED ARE REFERENCING THE 2010 FBC. THE |
| | CURRENT CODE IS THE FBC 5TH EDITION (2014). REVISE |
| | INFORMATION ON SHEET A-1 AND A-3. CHAPTER 553 F.S. |
| | |
| | 2- ACCORDING TO SEC. R301.2.1.4 OF FBC 5TH EDITION |
| | (2014) THIS BUILDING IS LOCATED IN EXPOSURE "C" NOT |
| | "B". REVISE INFORMATION ON SHEET A-1 AND A3 AS |
| | REQUIRED. |
| | |
| | 3- SHEET A-2: WINDOWS SPECIFIED FOR BEDROOM LOCATED |
| | ADJACENT TO THE GARAGE DON'T FIT ON THE OPENING SIZE |
| | SPECIFIED ON PLANS. REVISE AS REQUIRED. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | 4- CLARIFY IF PROPOSED ENTRY DOOR IS "INSWING" OR |
| | "OUTSWING". SHEET A-2 SHOWS "INSWING" ENTRY DOOR, WHILE |
| | SHEET S-1 SHOWS "OUTSWING" ENTRY DOOR. NOTE: TYPE OF |
| | SWING IS IMPORTANT FOR PROPER PRODUCT APPROVAL L |
| | REVIEW. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | NOTE: |
| | DESIGNER OF RECORD TO COORDINATE WITH PERSON PREPARING |
| | THE ENERGY CALCULATIONS TO AVOID CONFLICTS/DELAYS. |
| | DESIGNER OF RECORD TO PROVIDE ALL THE DETAILS AND |
| | SPECIFICATIONS REQUIRED BASED ON THE INFORMATION |
| | SPECIFIED ON THE ENERGY CALCULATIONS SUBMITTED. |
| | |
| | 5- REVISE ENERGY CALCULATIONS SUBMITTED; |
| | A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM |
| | INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE |
| | AND JURISDICTION. CLARIFY WHY THE PROJECT NAME IS 2416 |
| | S. OLIVE AVE, WHILE THE STREET ADDRESS IS 2417 S. OLIVE |
| | AVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). |
| | |
| | B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | HOW THE EXISTING HOUSE COMPLIES WITH THE R-2 INSULATION |
| | ON THE SLAB ON GRADE EDGE INSULATION SPECIFIED ON ITEM |
| | #8. SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | HOW THE EXISTING HOUSE COMPLIES WITH THE R-8 CONCRETE |
| | BLOCK EXTERIOR INSULATION SPECIFIED ON ITEM #9. SEC. |
| | R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | HOW THE EXISTING HOUSE COMPLIES WITH THE R-38 CEILING |
| | INSULATION SPECIFIED ON ITEM #10. SEC. R405.4.3 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | E) COOLING AND HEATING INFORMATION SHOWN ON ITEMS #12 |
| | AND #13 DON'T MATCH EQUIPMENT SIZING CALCULATIONS |
| | SUBMITTED. REVISE AS REQUIRED, INCLUDING THE SEER. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | F) REVISE TYPE OF HOT WATER SYSTEM SPECIFIED ON ITEM |
| | #14. PLANS SUBMITTED DON'T SPECIFY ELECTRIC SYSTEM. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | G) CEILING FANS CREDIT IS TAKEN ON ITEM #15. SPECIFY ON |
| | PLANS SIZE AND LOCATION OF CEILING FANS AS REQUIRED BY |
| | SEC. R405.7.6 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | H) OWNER /AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS |
| | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | |
| | I) NUMBER OF OCCUPANTS SPECIFIED UNDER "SPACES" ON PAGE |
| | 2 OF 4 DOESN'T MATCH NUMBER OF OCCUPANTS SHOWN ON THE |
| | EQUIPMENT SIZING CALCULATIONS SUBMITTED. REVISE AS |
| | REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | |
| | J) TYPE OF ROOF SPECIFIED UNDER "ROOF" ON PAGE 2 OF 4 |
| | DOESN'T MATCH TYPE OF ROOF SHOWN ON PLANS. REVISE AS |
| | REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | |
| | K) ACCORDING TO SEC. R806.2 FBC-RESIDENTIAL, THE |
| | REQUIRED ATTIC VENTILATION RATIO IS 1/150. ATTIC |
| | INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC |
| | VENTILATION RATIO. PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS SHOWING HOW THE EXISTING HOUSE COMPLIES |
| | WITH THE 1/300 RATIO. SEE SEC. R806.2 FBC-RESIDENTIAL |
| | FOR THE REQUIREMENTS REQUIRED TO MEET THIS VENT RATIO |
| | AND PROVIDE THE REQUIRED DOCUMENTATION. |
| | |
| | L) REVISE THE WINDOWS/DOORS OVERHANG SEPARATION |
| | SPECIFIED ON SHEET 3 OF 4 TO MATCH PLANS. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | M) DOORS INFORMATION ON PAGE 3 OF 4 SPECIFIES INSULATED |
| | DOORS. TYPE OF DOORS DON'T MATCH TYPE OF DOORS |
| | SPECIFIED ON PLANS AND PRODUCT APPROVALS SUBMITTED. |
| | DOOR WITH GLAZING NEEDS TO BE SPECIFIED ON WINDOWS AREA |
| | AS REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | |
| | N) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED |
| | BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | NOTE: |
| | LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| | SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL |
| | BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT USING |
| | THE PROGRAM DEFAULT FACTORS. |
| | |
| | 6-CEILING FANS CREDIT IS TAKEN ON ITEM #15. DESIGNER OF |
| | RECORD TO SPECIFY ON PLANS SIZE AND LOCATION OF CEILING |
| | FANS AS REQUIRED BY SEC. 103.2 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | |
| | 7- ACCORDING TO SEC. R806.2 FBC-RESIDENTIAL, THE |
| | REQUIRED ATTIC VENTILATION RATIO IS 1/150. ATTIC |
| | INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC |
| | VENTILATION RATIO. DESIGNER OF RECORD TO PROVIDE |
| | COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW THE |
| | EXISTING HOUSE COMPLIES WITH THE 1/300 RATIO AS |
| | REQUIRED BY SEC. R806.2 FBC-RESIDENTIAL. |
| | |
| | 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR "INSWING" ENTRY DOOR AS SHOWN |
| | ON PLANS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |