| 2016-11-09 15:05:25 | 550 OKEECHOBEE BOULEVARD #120 | | | PERMIT #16110155 | | | FIRE DEPT REVIEW COMMENTS | | | | | | NO FIRE ALARM NOTIFICATION DEVICES OR SMOKE DETECTOR | | | LAYOUT PROVIDED. | | | | | | NO FIRE SPRINKLER DESIGN PROVIDED. THE SPACE IS BEING | | | CONVERTED FROM A BUSINESS OCCUPANCY TO A RESIDENTIAL | | | OCCUPANCY REQUIRING RESIDENTIAL STYLE SPRINKLERS IN | | | LIEU OF COMMERCIAL STYLE SPRINKLERS. | | | | | | WHAT OCCUPANCIES EXIST ABOVE AND ADJACENT TO THE NEW | | | APARTMENT? WHAT FIRE RATED SEPARATION IS BEING PROVIDED | | | OR IS EXISTING? | | | | | | WHERE DO THE APARTMENT EXIT DOORS LEAD? EXTERIOR? | | | INTERIOR CORRIDOR? | | | | | | INSUFFICIENT INFORMATION PROVIDED ON THE PLANS TO | | | PROVIDE A COMPLETE FIRE AND LIFE SAFETY REVIEW. | | | ADDITIONAL REVIEW COMMENTS MAY BE GENERATED DURING PLAN | | | RESUBMITTAL. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WPB FIRE RESCUE | | | [email protected] |
|