2016-11-09 18:42:36REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO'S
  
 1] GFCI PROTECTRION REQUIRED IN KITCHEN PER NEC
 210.8(A)
 2] MINIMUM 2 SMALL APPLIANCE 20 AMP CIRCUITS REQUIRED
 PER NEC 210.52