| Notes |
| Date |
Text |
| 2016-11-09 08:08:16 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16110097 | | | 11/9/16 | | | | | | 1) SHEET M-1: PLEASE IDENTIFY ALL THE ROOMS AND SPACES | | | ON THE PLAN- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC. | | | | | | 2) M-1: PROVIDE THE MAKES AND MODELS AND COOLING AND | | | HEATING CAPACITIES OF THE EXISTING AC SYSTEMS. | | | | | | 3) M-1: CORRECT NOTE #2 INDICATING 1152 SF TO SQUARE | | | INCHES. | | | | | | 4) REFER TO SECTION 602.1: PLENUMS SHALL BE LIMITED TO | | | ONE FIRE AREA. PROVIDE A DUCTED RETURN TO AC-2 FROM THE | | | WEST TENANT SPACE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|