| 2016-11-09 10:42:53 | JOB PERMIT NUMBER: 16110097 |
| | JOB ADDRESS: 400 S AUSTRALIAN AVE |
| | WEST PALM BEACH FLORIDA |
| | DATE: NOVEMBER 9, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| | AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. |
| | |
| | 1] CLARIFY IF A NEW ELECTRIC DRINKING FOUNTAIN IS BEING |
| | INSTALLED? IF SO GFCI PROTECTION WILL BE REQUIRED PER |
| | NEC 422.52. |
| | |
| | 2] PLEASE PROPERLY ADJUST CIRCUIT DESIGNATION LABELING |
| | TO MATCH PANEL "L". FBC-107 |
| | |
| | 3] PLEASE LABEL & IDENTIFY ALL ROOMS ON THE PLAN. |
| | FBC-107 |
| | |
| | 4] ALL WORK ASSOCIATED WITH LOW VOLTAGE SYSTEM WILL BE |
| | UNDER A SEPARATE PERMIT. A NOTE WILL SUFFICE. |
| | |
| | 5] PROVIDE A RISER DIAGRAM TO INCLUDE THE RELOCATION OF |
| | PANEL "L" SHOW WIRE & CONDUIT SIZES. IF THE EXISTING |
| | PANEL CABINET WILL BE USED AS A J-BOX ALL PENETRATIONS |
| | MUST BE SEALED & THE ENCLOSURE SHALL BE MARKED WITH A |
| | WARNING LABEL IDENTIFYING THE DISCONNECTING MEANS PER |
| | NEC 312.8(3). |
| | |
| | 6] ADD A GENERAL ELECTRICAL NOTE STATING THAT AT LEAST |
| | 50 % OF ALL 125 V 15 & 20 AMP RECEPTACLES INSTALLED IN |
| | PRIVATE OR OPEN OFFICES INCLUDING MODULAR PARTITIONS |
| | SHALL BE CONTROLLED BY AN AUTOMATIC CONTROL DEVICE PER |
| | FBC-E SECTION C405.7.1 CONFORMANCE WITH ASHREA 90.1, |
| | 8.4.2. |
| | |
| | 7] SHOW LIGHTING CONTROLS IN OFFICE AREAS; PLEASE |
| | REFERENCE FBC-E SECTION C405 FOR LIGHTING REDUCTION, |
| | AUTOMATIC TIME SWITCHES, OCCUPANCY SENSOR & ETC. |
| | |
| | 8] THE NEW LOCATION OF PANEL "L" MAY COMPROMISE THE |
| | FIRE RATING OF THE WALL. PLEASE PROVIDE CALRIFICATION |
| | IF THE INSTALLATION IS SURFACE MOUNTED OR SHOW |
| | COMPLIANCE WITH FBC-714 & NEC 300.21. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| | DIRECTLY. |
| | |
| | 1ST REVIEW FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |