| Plan Review Notes For Permit 16110075 |
| Permit Number |
16110075 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-04 12:21:17 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16110075 | | | 11/4/16 | | | | | | 1) THE REVISE PLANS SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION | | | 107.2.1 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE. | | | | | | 2) DUE TO THE CHANGES IN AC SYSTEMS REVISED ENERGY | | | CALCULATIONS AND ELECTRICAL PLANS MUST BE SUBMITTED. | | | | | | 3) THE REVISED PLAN INDICATES 1765 CFMS OF AIR | | | DISTRIBUTION FOR AHU-1 WHICH IS NOW A 4-TON. PROVIDE | | | SPECS TO INDICATE THE SYSTEM CAN PRODUCE THAT AMOUNT. | | | | | | 4) THE NEW 4-TON AC-3 SYSTEM IS OVERSIZED PER THE AC | | | CALCULATIONS- REFER TO SECTION R403.6.1.1 FBC-14 ENERGY | | | CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|