Plan Review Notes
Plan Review Notes For Permit 16110075
Permit Number 16110075
Review Stop M
Sequence Number 1
Notes
Date Text
2016-11-04 12:21:171ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110075
 11/4/16
  
 1) THE REVISE PLANS SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION
 107.2.1 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE.
  
 2) DUE TO THE CHANGES IN AC SYSTEMS REVISED ENERGY
 CALCULATIONS AND ELECTRICAL PLANS MUST BE SUBMITTED.
  
 3) THE REVISED PLAN INDICATES 1765 CFMS OF AIR
 DISTRIBUTION FOR AHU-1 WHICH IS NOW A 4-TON. PROVIDE
 SPECS TO INDICATE THE SYSTEM CAN PRODUCE THAT AMOUNT.
  
 4) THE NEW 4-TON AC-3 SYSTEM IS OVERSIZED PER THE AC
 CALCULATIONS- REFER TO SECTION R403.6.1.1 FBC-14 ENERGY
 CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved