2017-02-08 06:42:391) SHT. P3.1 - THE PLAN SHOWS A CONCRETE VAULT TYPE
 GREASE INTERCEPTOR AND ALSO AN ALL STEEL WATTS (
 HYDROMECHANICAL ?) GREASE INTERCEPTOR.WHICH TANK IS
 BEING USED? AT THIS POINT I HAVE NO IDEA AS TO HOW THE
 SIZE OF THE WATTS INTERCEPTOR WAS DETERMINED, HOW THE
 FLOW RATE WAS DETERMINED, THE GREASE CAPACITY,
 ETC.SUBMIT SIZING CALCULATIONS FOR THE WATTS
 INTERCEPTOR. 2014 FBC-PLUMBING SEC.1003.2, 1003.3.4,
 1003.3.4.1.
 2) THE CONCRETE INTERCEPTOR SHALL COMPLY WITH THE
 DESIGN REQUIREMENTS OF FL. ADMIN. CODE RULE 64E-6.013
 (7) (A). THE INLET INVERT SHALL DISCHARGE A MINIMUM 2
 1/2 INCHES ABOVE THE LIQUID LEVEL LINE AND THE OUTLET
 PIPE SHALL HAVE A TEE WITH A MINIMUM DIAMETER OF 4
 INCHES THAT EXTENDS TO WITHIN 8 INCHES OF THE BOTTOM OF
 THE TANK.
 3) THE MINIMUM CAPACITY OF A CONCRETE VAULT TYPE GREASE
 INTERCEPTOR SHALL BE 750 GALLONS. F.A.C. RULE 64E-6.013
 (7) (D).
 4) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE SIDE OF
 THE GREASE INTERCEPTOR.
 5) A LAUNDRY INTERCEPTOR IS REQUIRED FOR THE LAUNDRY
 AREA PERR 2014 FBC-PLUMBING SEC. 1003.6. THIS ITEM WAS
 OVERLOOKED DURING THE PREVIOUS REVIEWS.
  