Plan Review Notes
Plan Review Notes For Permit 16110067
Permit Number 16110067
Review Stop P
Sequence Number 2
Notes
Date Text
2017-01-03 06:47:531) THE PLUMBING PLANS SHALL BE SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD PER THE FL. ADMIN. CODE
 RULE 61G15-23.001. THE SUBMITTED PLANS ARE COPIES OF
 THE SEAL AND SIGNATURE. 2ND REQUEST.
 2) SUBMIT A KITCHEN EQUIPMENT SCHEDULE / LIST FOR
 REVIEW. THE LIST SHALL SHOW THE WATER, DRAIN AND GAS
 SUPPLY SIZES TO THE EQUIPMENT.
 3) SHT.P2.0 - KEYED NOTE #6 REFERS TO A TWO WAY
 CLEANOUT BUT IT IS ALSO SHOWN AT THE GAS LINE. WHICH IS
 IT? CLARIFY. 2ND REQUEST.
 4) SHT. P3.0 - INDICATE THE SIZE OF THE EXPANSION TANK
 ON THE WATER HEATER DETAIL. 2ND. REQUEST.
 5) THE ICEMAKER AND JUICE MACHINE EACH SHALL BE
 EQUIPPED WITH BACKFLOW PREVENTERS, NOT ONE DEVICE FOR
 BOTH APPLIANCES.2014 FBC-PLUMBING SECS.608.3,
 608.16.10.
 6) SUBMIT A DETAIL AND SIZING CALCULATIONS FOR THE
 GREASE INTERCEPTOR.2014 FBC-PLUMBING SEC.1003.2. IF THE
 UNIT IS A HYDROMECHANICAL TYPE INTERCEPTOR, SUBMIT
 SIZING CALCULATIONS DONE BY THE MANUFACTURER.
 HYDROMECHANICAL GREASE INTERCEPTORS SHALL COMPLY WITH
 2014 FBC-PLUMBING SEC.1003.3.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  