| Plan Review Notes For Permit 16110067 |
| Permit Number |
16110067 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-01-03 06:47:53 | 1) THE PLUMBING PLANS SHALL BE SIGNED AND SEALED BY THE | | | DESIGN PROFESSIONAL OF RECORD PER THE FL. ADMIN. CODE | | | RULE 61G15-23.001. THE SUBMITTED PLANS ARE COPIES OF | | | THE SEAL AND SIGNATURE. 2ND REQUEST. | | | 2) SUBMIT A KITCHEN EQUIPMENT SCHEDULE / LIST FOR | | | REVIEW. THE LIST SHALL SHOW THE WATER, DRAIN AND GAS | | | SUPPLY SIZES TO THE EQUIPMENT. | | | 3) SHT.P2.0 - KEYED NOTE #6 REFERS TO A TWO WAY | | | CLEANOUT BUT IT IS ALSO SHOWN AT THE GAS LINE. WHICH IS | | | IT? CLARIFY. 2ND REQUEST. | | | 4) SHT. P3.0 - INDICATE THE SIZE OF THE EXPANSION TANK | | | ON THE WATER HEATER DETAIL. 2ND. REQUEST. | | | 5) THE ICEMAKER AND JUICE MACHINE EACH SHALL BE | | | EQUIPPED WITH BACKFLOW PREVENTERS, NOT ONE DEVICE FOR | | | BOTH APPLIANCES.2014 FBC-PLUMBING SECS.608.3, | | | 608.16.10. | | | 6) SUBMIT A DETAIL AND SIZING CALCULATIONS FOR THE | | | GREASE INTERCEPTOR.2014 FBC-PLUMBING SEC.1003.2. IF THE | | | UNIT IS A HYDROMECHANICAL TYPE INTERCEPTOR, SUBMIT | | | SIZING CALCULATIONS DONE BY THE MANUFACTURER. | | | HYDROMECHANICAL GREASE INTERCEPTORS SHALL COMPLY WITH | | | 2014 FBC-PLUMBING SEC.1003.3.4. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|