| Plan Review Notes For Permit 16110067 |
| Permit Number |
16110067 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-12-19 16:08:19 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16110067 | | | 12/19/16 | | | | | | 1) 2ND REQUEST FOR COOLING AND HEATING CALCULATIONS FOR | | | RTU-1. | | | | | | 2) 2ND REQUEST FOR OWNER/AGENT SIGNATURE ON THE ENERGY | | | CALCULATIONS | | | | | | 3) SMOKE DAMPERS ARE REQUIRED FOR THE DUCTS PENETRATING | | | THE CORRIDOR AND UTILITY ROOM SMOKE PARTITIONS. | | | | | | 4) IN REFERENCE TO THE NARRATIVE RESPONSE FROM THE | | | ARCHITECT TO COMMENT #4 FROM THE 1ST REVIEW, PLEASE | | | PROVIDE A KEYED NOTE ON THE PLAN TO CLARIFY THE FAN | | | SHUTDOWN PROCEDURE UPON DETECTION OF SMOKE. | | | | | | 5) IN REFERENCE TO RESPONSE TO COMMENT #8 FROM THE 1ST | | | REVIEW PLEASE INDICATE HOW COMBUSTION AIR IS BEING | | | PROVIDED FOR THE COOKING APPLIANCES AND SHOW | | | CALCULATIONS. | | | | | | 6) IN REFERENCE TO COMMENT #7 FROM THE 1ST REVIEW | | | PLEASE INDICATE HOW DRYER MAKEUP AIR IS BEING PROVIDED | | | AND SHOW CALCULATIONS. PLEASE SUBMIT MANUFACTURER'S | | | SPECS FOR THE DRYERS. | | | | | | 7) THE REQUESTED WIND LOAD ENGINEERING WAS NOT | | | PROVIDED- PLEASE COMPLY. | | | | | | 8) THE MECHANICAL PLANS HAVE COPIED ENGINEER'S SEALS | | | AND SIGNATURES. ORIGINALS ARE REQUIIRED PER SECTION | | | 61G15-23.002 FAC. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|