| 2017-01-04 11:29:42 | 1) SHT.P4.1 - A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. A SHUTOFF VALVE |
| | SHALL BE LOCATED BETWEEN THE GAS METER AND THE NEW |
| | REGULATOR. 2ND REQUEST. FBC FUEL GAS SEC.409.4. |
| | 2) SHT. P4.1 - SHOW THE CORRECT DISTANCE FROM THE NEW |
| | GAS REGULATOR TO THE MOST REMOTE OUTLET ON THE SYSTEM |
| | WHICH APPEARS TO BE THE GENERATOR. THE PLANS NOTE THE |
| | LONGEST RUN OF GAS PIPING FROM THE NEW GAS REGULATOR TO |
| | THE MOST REMOTE GAS OUTLET AS 195 FEET. THE FOLLOWING |
| | LENGTHS OF PIPE MEASUREMENTS SHOWN ON THE PLANS TO THE |
| | MOST REMOTE GAS OUTLET ARE AS FOLLOWS: |
| | 3' + 5' + 15'- 6" + 56' +140' + 15'- 6" +3' . PLEASE |
| | EXPLAIN HOW THIS EQUALS 195 FEET WHEN I CALCULATE 238 |
| | FEET. 2ND REQUEST.2014 FBC-FUEL GAS SEC.402.4.1. A |
| | COMPREHENSIVE GAS REVIEW CANNOT BE PERFORMED UNTIL THE |
| | CORRECT DISTANCE IS PROVIDED AND THE PLANS ARE |
| | CORRECTED. IF THE DISTANCE IS 238 FEET THE ENTIRE GAS |
| | SYSTEM IS UNDERSIZED FOR GALVANIZED PIPE. SIZE ALL |
| | SECTIONS OF THE GAS RISER IN ACCORDANCE WITH THE |
| | APPLICABLE SIZING TABLES IN THE FUEL GAS CODE. |
| | 3) SHT. P4.1 - THE GAS RISER STILL SHOWS THE |
| | UNDERGROUND PIPE AS GALVANIZED ( LABELED "G") BUT THE |
| | TEXT STATES THE UNDERGROUND PIPE TO BE PE. CLEARLY |
| | IDENTIFY THE TYPE OF PIPING IN THE DIFFERENT AREAS ON |
| | THE GAS RISER. 2ND REQUEST. 2014 FBC-FUEL GAS |
| | SEC.404.11. |
| | 4) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | KITCHEN EQUIPMENT AND ALL OTHER GAS APPLIANCES / |
| | EQUIPMENT PER THE 2014 FBC-FUEL GAS SEC.304.1.WHERE |
| | COMBUSTION AIR IS PROVIDED BY THE BUILDING'S MECHANICAL |
| | VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE |
| | SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR. 2014 FBC-FUEL GAS SEC. |
| | 304.9.3.THE CODE SECTION YOUR DESIGN IS BASED UPON |
| | REFERS TO THE SUPPLY OF COMBUSTION AIR BY MEANS OF A |
| | FAN/BLOWER THAT RUNS WHEN ANY OF THE SERVED APPLIANCES |
| | ARE IN A FIRING CYCLE. HOW ARE TRANSFER GRILLS AND |
| | DUCTS MEETING THIS REQUIREMENT? |
| | 5) SUBMIT A DETAIL SHOWING THE TYPE, SIZE, LOCATION AND |
| | TERMINATION OF GAS VENTS PER 2014 FBC-FUEL GAS SECS. |
| | 502 THRU 505. THIS HAS NOT BEEN DONE. 2ND REQUEST. |
| | 6) SHOW THE EMERGENCY SHUT DOWN VALVE AND THE MANUAL |
| | SHUTOFF VALVE FOR THE GAS TO THE GAS COOKING APPLIANCES |
| | IN THE KITCHEN. THE LOCATION OF THE EMERGENCY SHUT DOWN |
| | AND THE MANUAL ACTIVATION VALVE SHALL BE LOCATED IN |
| | ACCORDANCE WITH NFPA 96-08 SECS. 10.4 & 10.5. 2ND |
| | REQUEST. THE EMERGENCY SHUT DOWN VALVE SHALL BE LOCATED |
| | BELOW THE CEILING AND THE MANUAL SHUTOFF VALVE SHALL BE |
| | UPSTREAM OF THE EMERGENCY SHUT DOWN VALVE WITH A UNION |
| | LOCATED DOWNSTREAM OF THE MANUAL VALVE. THESE ITEMS |
| | SHALL BE SHOWN ON THE GAS PLAN. 2ND REQUEST. |
| | 7) APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND |
| | SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. SUBMIT WIND LOAD ANCHORING |
| | DETAILS FOR THE GENERATOR. 2ND REQUEST. |
| | 8) SHOW THE GAS PIPING TO THE WATER HEATER ON SHT. |
| | P3.0. |
| | 9) ARE THE DRYERS LOCATED IN ROOM #118 GAS OR ELECTRIC? |
| | IF GAS, SHOW THE DRYERS AND THE BTU LOAD OF EACH ONE ON |
| | THE GAS RISER, SUBMIT COMBUSTION AIR CALCULATIONS AND |
| | DETAILS ON THE VENTS.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) THE PLUMBING PLANS SHALL BE SIGNED AND SEALED BY |
| | THE DESIGN PROFESSIONAL OF RECORD PER THE FL. ADMIN. |
| | CODE RULE 61G15-23.001. THE SUBMITTED PLANS ARE COPIES |
| | OF THE SEAL AND SIGNATURE. 2ND REQUEST. |
| | |