Plan Review Notes
Plan Review Notes For Permit 16110067
Permit Number 16110067
Review Stop R
Sequence Number 1
Notes
Date Text
2016-11-17 07:41:44****CORRECTIONS****
 ROOF PLAN REVIEW
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
  
 1. NOA #16-0413.11, JOHNS MANVILLE BUILT-UP ROOFING
 SYSTEMS OVER CONCRETE DECKS, WAS REVIEWED BY DOR AND
 SUBMITTED. THIS PRODUCT IS ALSO REFERENCED BY ARCHITECT
 ON SHEET A2.1.
  
 IN ORDER TO OBTAIN A "PASSED" ROOFING REVIEW STOP,
 INDICATE THE APPROVED ASSEMBLY PROPOSED.
  
 OR, UPON REQUEST, APPLICANT MAY ELECT TO DEFER THIS
 SUBMITTAL, AND AN "N" WILL BE ENTERED FOR THE ROOF
 REVIEW. THE PERMIT WILL BE ISSUED WITH PROVISO THAT,
 PRIOR TO INSTALLATION, THE ASSEMBLY PROPOSED, ALONG
 WITH ENGINEERING FOR ENHANCED FASTENING IF APPLICABLE,
 BE SUBMITTED AS A REVISION (WITH APPLICABLE REVISION
 FEES).
  
  
  