| 2016-11-20 06:37:30 | PLUMBING PLAN REVIEW 11/20/16 TIM LARGE |
| | |
| | 1) SHT. SP 1 SHOWS AN EMERGENCY GENERATOR. INDICATE ON |
| | THE PLAN IF IT IS NEW OR EXISTING. IF NEW, SUBMIT TWO |
| | COPIES OF FFULL DOCUMENTATION FOR THE GENERATOR ( |
| | MANUFACTURER'S SPECIFICATIONS, MANUAL, ETC., ) OR PLACE |
| | A NOTE ON THE PLAN THAT THE GENERATOR WILL BE DDONE |
| | UNDER A SEPARATE PERMIT. WPB AMEND. TO 2014 FBC SEC. |
| | 107.2.1. |
| | 2) A SEPARATE PERMIT IS REQUIRED FOR THE IRRIGATION |
| | SYSTEM AS NO IRRIGATION PLANS HAVE BEEN SUBMITTED. |
| | 3) THIS APPEARS TO BE A CHANGE OF OCCUPANCY. INDICATE |
| | THIS ON THE PLANS AND LIST THE PREVIOUS OCCUPANCY ON |
| | THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) SHT. LS 1.1 NOTES 43 BEDS BUT THE PLAN SHOWS 44 BEDS |
| | AND SHT. SP 1 NOTES 46 BEDS. CLARIFY AND PLACE THE |
| | CORRECT NUMBER OF BEDS ON THE NOTED SHEETS. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 5) SHT. A8.1 - ELEV. #1 - THE GRAB BAR ON THE SIDE WALL |
| | SHALL BE LOCATED PER 2014 FBC-ACCESS. SEC.604.5.1 AND |
| | FIGURE 604.5.1. THE GRAB BAR SHALL EXTEND A MINIMUM OF |
| | 54 INCHES FROM THE REAR WALL. |
| | 6) SHT. A8..1 - ELEV. #3 SHOWS 2'-5" MINIMUM TO THE |
| | BOTTOM OF THE LAVATORY APRON AND ELEVATION #2 SHOWS |
| | 2'-3". CLARIFY. |
| | 7) SHT.A8.1 - ELEV.#1 - THE LOCATION OF THE TOILET |
| | PAPER DISPENSER SHALL COMPLY WITH FBC-ACCESS. |
| | SEC.604.7. |
| | 8) SHT. A8.1 - ELEV. #1 & #4 - THE HEIGHT OF THE WATER |
| | CLOSET SHALL COMPLY WITH FBC-ACCESS. SEC.604.4. |
| | 9) A8.1 - ELEV.#1 & #5 - GRAB BARS SHALL BE MEASURED TO |
| | THE TOP OF THE GRIPPING SURFACE.FBC-ACCESS. SEC. 609.4. |
| | 10) AT LEAST ONE WASHING MACHINE AND DRYER SHALL COMPLY |
| | WITH FBC-ACCESS. SECS.214 & 611. |
| | 11) SUBMIT DETAILS / ELEVATIONS FOR THE ACCESSIBLE |
| | SHOWERS.COMPLY WITH 2014 FBC-ACCESS. SEC. 608. |
| | 12) SUBMIT A ROOF SCUPPER DETAIL FOR REVIEW. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 13) PROVIDE DETAILS FOR OVERFLOW DRAINAGE IN ACCORDANCE |
| | WITH THE 2014 FBC SEC.1503.4.2.1. |
| | 14) THE PLUMBING PLANS SHALL BE SIGNED AND SEALED BY |
| | THE DESIGN PROFESSIONAL IN ACCORDANCE WITH THE FL. |
| | ADMIN. CODE RULE 61G15-23.001. |
| | 15) SUBMIT A KITCHEN EQUIPMENT LIST FOR REVIEW. THE |
| | LIST SHALL SHOW WATER, DRAIN ANDD GAS SUPPLY SIZES TO |
| | THE EQUIPMENT. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 16) SHT. P4.0 - SHOW ALL INDIRECT WASTES DRAINS ON THE |
| | PLUMBING RISER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 17) SHT. P4.0 - THE SANITARY RISER REFERS TO CIVIL |
| | DRAWINGS FOR THE CONTINUATION OF THE SANITARY AND |
| | GREASE LINES. THERE ARE NO CIVIL DRAWINGS IN THE PLANS. |
| | CLARIFY. |
| | 18) SHOW THE CLEAR INSIDE DIMENSIONS (L X W) OF THE |
| | SHOWERS IN THE TYPICAL PATIENT ROOMS. |
| | 19) SUBMIT AN ENLARGED FLOOR PLAN FOR THE ACCESSIBLE |
| | TOILET ROOMS FOR THE STAFF/COMMON AREA TOILETS AND ALSO |
| | THE PATIENT TOILET ROOM INCLUDING THE ACCESSIBLE AND |
| | NON-ACCESSIBLE TOILET ROOMS. SHOW ALL FIXTURE |
| | CLEARANCES, INSIDE CLEAR DIMENSIONS OF THE SHOWER (L X |
| | W), HEIGHT AND LOCATION OF CONTROLS, ETC. COMPLY WITH |
| | FBC-ACCESS. SEC. 608 & 2014 FPC. |
| | 20) SHT. P2.0 - KEYED NOTE #6 REFERS TO A TWO WAY |
| | CLEANOUT BUT IT IS SHOWN AT THE GAS LINE. CLARIFY. |
| | 21) SHT. P3.0 - INDICATE THE SIZE OF THE EXPANSION TANK |
| | ON THE WATER HEATER DETAIL. |
| | 22) SHT. P3.0 - THE RELIEF LINE FOR THE WATER HEATER |
| | SHALL TERMINATE IN ACCORDANCE WITH 2014 FPC SEC.504.6 |
| | (1-13). |
| | 23) THE WASHING MACHINES SHALL DISCHARGE INTO A 3 INCH |
| | WASTE STACK PER 2014 FBC-PLUMBING SEC.406.2. |
| | 24) SHT. P4.0 - THE INSTALLATION OF BACK TO BACK WATER |
| | CLOSETS SHALL COMPLY WITH FPC SEC.706.3. |
| | 25) SHT. P4.0 - THE IDENTIFICATION ( LOCATION) OF THE |
| | WATER CLOSET AND THE LAVATORY ON THE SANITARY RISER IN |
| | ROOM #3 ( 119 ) DOES NOT CORRELATE WITH THE FLOOR PLAN |
| | ON SHT. P2.0. THEY ARE REVERSED. THE SAME SITUATION |
| | OCCURS ON THE WATER RISER AND ALSO FOR ROOM #12 (129 ). |
| | 26) CLEARLY IDENTIFY THE SECTIONS OF THE WATER AND |
| | SANITARY RISERS TO CORRELATE WITH THE RISER TAGS SHOWN |
| | ON P1.0 & P2.0. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 27) THE ICEMAKER AND JUICE MACHINE SHALL BE EQUIPPED |
| | WITH BACKFLOW PREVENTERS PER THE FPC SEC.608.3, |
| | 608.16.10. |
| | 28) SHT. P4.1 - SIZE THE WATER SUPPLY LINE TO THE SINK, |
| | ICE MAKER AND JUICE DISPENSER AND ALSO THE INDIVIDUAL |
| | LINES TO EACH APPLIANCE. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |