2016-11-20 06:37:30PLUMBING PLAN REVIEW 11/20/16 TIM LARGE
  
 1) SHT. SP 1 SHOWS AN EMERGENCY GENERATOR. INDICATE ON
 THE PLAN IF IT IS NEW OR EXISTING. IF NEW, SUBMIT TWO
 COPIES OF FFULL DOCUMENTATION FOR THE GENERATOR (
 MANUFACTURER'S SPECIFICATIONS, MANUAL, ETC., ) OR PLACE
 A NOTE ON THE PLAN THAT THE GENERATOR WILL BE DDONE
 UNDER A SEPARATE PERMIT. WPB AMEND. TO 2014 FBC SEC.
 107.2.1.
 2) A SEPARATE PERMIT IS REQUIRED FOR THE IRRIGATION
 SYSTEM AS NO IRRIGATION PLANS HAVE BEEN SUBMITTED.
 3) THIS APPEARS TO BE A CHANGE OF OCCUPANCY. INDICATE
 THIS ON THE PLANS AND LIST THE PREVIOUS OCCUPANCY ON
 THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHT. LS 1.1 NOTES 43 BEDS BUT THE PLAN SHOWS 44 BEDS
 AND SHT. SP 1 NOTES 46 BEDS. CLARIFY AND PLACE THE
 CORRECT NUMBER OF BEDS ON THE NOTED SHEETS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 5) SHT. A8.1 - ELEV. #1 - THE GRAB BAR ON THE SIDE WALL
 SHALL BE LOCATED PER 2014 FBC-ACCESS. SEC.604.5.1 AND
 FIGURE 604.5.1. THE GRAB BAR SHALL EXTEND A MINIMUM OF
 54 INCHES FROM THE REAR WALL.
 6) SHT. A8..1 - ELEV. #3 SHOWS 2'-5" MINIMUM TO THE
 BOTTOM OF THE LAVATORY APRON AND ELEVATION #2 SHOWS
 2'-3". CLARIFY.
 7) SHT.A8.1 - ELEV.#1 - THE LOCATION OF THE TOILET
 PAPER DISPENSER SHALL COMPLY WITH FBC-ACCESS.
 SEC.604.7.
 8) SHT. A8.1 - ELEV. #1 & #4 - THE HEIGHT OF THE WATER
 CLOSET SHALL COMPLY WITH FBC-ACCESS. SEC.604.4.
 9) A8.1 - ELEV.#1 & #5 - GRAB BARS SHALL BE MEASURED TO
 THE TOP OF THE GRIPPING SURFACE.FBC-ACCESS. SEC. 609.4.
 10) AT LEAST ONE WASHING MACHINE AND DRYER SHALL COMPLY
 WITH FBC-ACCESS. SECS.214 & 611.
 11) SUBMIT DETAILS / ELEVATIONS FOR THE ACCESSIBLE
 SHOWERS.COMPLY WITH 2014 FBC-ACCESS. SEC. 608.
 12) SUBMIT A ROOF SCUPPER DETAIL FOR REVIEW. WPB AMEND.
 TO FBC SEC. 107.2.1.
 13) PROVIDE DETAILS FOR OVERFLOW DRAINAGE IN ACCORDANCE
 WITH THE 2014 FBC SEC.1503.4.2.1.
 14) THE PLUMBING PLANS SHALL BE SIGNED AND SEALED BY
 THE DESIGN PROFESSIONAL IN ACCORDANCE WITH THE FL.
 ADMIN. CODE RULE 61G15-23.001.
 15) SUBMIT A KITCHEN EQUIPMENT LIST FOR REVIEW. THE
 LIST SHALL SHOW WATER, DRAIN ANDD GAS SUPPLY SIZES TO
 THE EQUIPMENT. WPB AMEND. TO FBC SEC. 107.2.1.
 16) SHT. P4.0 - SHOW ALL INDIRECT WASTES DRAINS ON THE
 PLUMBING RISER. WPB AMEND. TO FBC SEC. 107.2.1.
 17) SHT. P4.0 - THE SANITARY RISER REFERS TO CIVIL
 DRAWINGS FOR THE CONTINUATION OF THE SANITARY AND
 GREASE LINES. THERE ARE NO CIVIL DRAWINGS IN THE PLANS.
 CLARIFY.
 18) SHOW THE CLEAR INSIDE DIMENSIONS (L X W) OF THE
 SHOWERS IN THE TYPICAL PATIENT ROOMS.
 19) SUBMIT AN ENLARGED FLOOR PLAN FOR THE ACCESSIBLE
 TOILET ROOMS FOR THE STAFF/COMMON AREA TOILETS AND ALSO
 THE PATIENT TOILET ROOM INCLUDING THE ACCESSIBLE AND
 NON-ACCESSIBLE TOILET ROOMS. SHOW ALL FIXTURE
 CLEARANCES, INSIDE CLEAR DIMENSIONS OF THE SHOWER (L X
 W), HEIGHT AND LOCATION OF CONTROLS, ETC. COMPLY WITH
 FBC-ACCESS. SEC. 608 & 2014 FPC.
 20) SHT. P2.0 - KEYED NOTE #6 REFERS TO A TWO WAY
 CLEANOUT BUT IT IS SHOWN AT THE GAS LINE. CLARIFY.
 21) SHT. P3.0 - INDICATE THE SIZE OF THE EXPANSION TANK
 ON THE WATER HEATER DETAIL.
 22) SHT. P3.0 - THE RELIEF LINE FOR THE WATER HEATER
 SHALL TERMINATE IN ACCORDANCE WITH 2014 FPC SEC.504.6
 (1-13).
 23) THE WASHING MACHINES SHALL DISCHARGE INTO A 3 INCH
 WASTE STACK PER 2014 FBC-PLUMBING SEC.406.2.
 24) SHT. P4.0 - THE INSTALLATION OF BACK TO BACK WATER
 CLOSETS SHALL COMPLY WITH FPC SEC.706.3.
 25) SHT. P4.0 - THE IDENTIFICATION ( LOCATION) OF THE
 WATER CLOSET AND THE LAVATORY ON THE SANITARY RISER IN
 ROOM #3 ( 119 ) DOES NOT CORRELATE WITH THE FLOOR PLAN
 ON SHT. P2.0. THEY ARE REVERSED. THE SAME SITUATION
 OCCURS ON THE WATER RISER AND ALSO FOR ROOM #12 (129 ).
 26) CLEARLY IDENTIFY THE SECTIONS OF THE WATER AND
 SANITARY RISERS TO CORRELATE WITH THE RISER TAGS SHOWN
 ON P1.0 & P2.0. WPB AMEND. TO FBC SEC. 107.2.1.
 27) THE ICEMAKER AND JUICE MACHINE SHALL BE EQUIPPED
 WITH BACKFLOW PREVENTERS PER THE FPC SEC.608.3,
 608.16.10.
 28) SHT. P4.1 - SIZE THE WATER SUPPLY LINE TO THE SINK,
 ICE MAKER AND JUICE DISPENSER AND ALSO THE INDIVIDUAL
 LINES TO EACH APPLIANCE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW