Plan Review Notes
Plan Review Notes For Permit 16110067
Permit Number 16110067
Review Stop M
Sequence Number 1
Notes
Date Text
2016-11-09 12:17:081ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110067
 11/9/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR
 RTU-1. IT APPEARS THAT HP-1 & 2 WERE SIZED USING ONLY
 THE SENSIBLE COOLING LOADS SHOWN IN THE SUMMARY
 CALCULATIONS, AND NO HEATING LOAD CALCS ARE SHOWN.
  
 2) ENERGYGAUGE COMPLIANCE FORM: A) PROVIDE COMPLIANCE
 DATA FOR RTU-1. B) THE OWNER/AGENT MUST SIGN THE FORM-
 SEE PAGE 3.
  
 3) SHEETS M1 & M1.1: PLACE THE #3 KEYED NOTE AT EACH
 FIRE DAMPER LOCATION. PLEASE CLARIFY WHY FIRE DAMPERS
 ARE BEING INSTALLED AT DUCT PENETRATIONS INTO THE
 CORRIDOR SMOKE PARTITIONS- SEE SHEET A1.1 AND SECTION
 607.5.7. WHERE REQUIRED SMOKE DAMPERS SHALL BE
 INSTALLED IN SMOKE PARTITIONS.
  
 4) REFER TO SECTION 606.2.1- 606.2.2 AND PROVIDE DUCT
 SMOKE DETECTORS IN ALL RETURN AIR SYSTEMS OR AREA SMOKE
 DETECTORS THAT ARE CONNECTED TO THE FIRE ALARM. PLEASE
 NOTE THAT FIRE ALARM PLANS MUST BE SUBMITTED UNDER
 SEPARATE PERMIT, HOWEVER THE SMOKE DETECTORS MUST BE
 SHOWN ON BOTH SETS OF PLANS.
  
 5) M1.& M1.1: PLACE THE KEYED NOTE #9 AT EACH FAN COIL
 LOCATION AND PROVIDE A CONDENSATE DISPOSAL PLAN PER
 SECTION 307. SHOW THE PIPING RUNS, TYPE AND SIZES OF
 PIPINGS, AND DISCHARGE LOCATIONS.
  
 6) M1 & M1.1: PLACE THE KEYED NOTE #11 AT EACH
 REFRIGERATION DISTRIBUTION BOX SHOWN ON THE PLAN AND
 INDICATE HOW ACCESS WILL BE PROVIDED TO THE BOX.
  
 7) M1.1: SHOW THE DRYER EXHAUST DUCT RUNS AND PROVIDE
 DETAILS INCLUDING TYPES AND SIZES OF DUCTS, THE DUCT
 RUN LENGTHS AND TERMINATION LOCATIONS- SEE SECTION 504.
 A) PROVIDE MAKEUP AIR AND CALCULATIONS. B) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND PROVIDE AN EQUIPMENT
 SCHEDULE ON THE PLAN. C) INDICATE THE EXHAUST CFMS IN
 THE PRESSURIZATION CALCULATIONS ON M3.3.
  
 8) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED FOR THE
 COOKING APPLIANCES AND PROVIDE CALCULATIONS- SECTION
 304 FBC-14 FUEL GAS.
  
 9) M4: REFER TO SECTION 403.2.4.4 FBC-14 ENERGY
 CONSERVATION: IT APPEARS THAT THE CONTROL SEQUENCE FOR
 RTU-1 O/A IS NOT IN COMPLIANCE BECAUSE THE DAMPERS WILL
 REMAIN OPEN WHEN THE BUILDING IS UNOCCUPIED.
  
 10) REFER TO SECTION 301.15 AND PROVIDE WIND LOAD
 ENGINEERING FOR ANCHORING THE RTU AND HP-1 & 2. PLEASE
 INCLDUE THE DESIGN CRITERIA AS OUTLINED IN SECTUION
 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE