Plan Review Notes
Plan Review Notes For Permit 16110067
Permit Number 16110067
Review Stop G
Sequence Number 1
Notes
Date Text
2016-11-21 06:12:39GAS REVIEW
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS ON ALL GAS
 APPLIANCES / EQUIPMENT. EQUIPMENT SHALL BE LISTED AND
 LABELED PER 2014 FBC- FUEL GAS SEC.301.3. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
 2) A SHUTOFF VALVE IS REQUIRED ON THE SUPPLY SIDE OF
 THE METTER. FBC- FUEL GAS SEC.409.2.
 3) A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF OF EACH MP REGULATOR. FBC- FGC
 SEC.409.4.
 4) SHT. P4.01 - NOTE #3 - THE GAS CODE IN EFFECT IS THE
 2014 FBC-FUEL GAS CODE, NOT THE 2010. REVISE THE NOTE.
 5) THE GRILLE AND FIRE PIT IS NOT LISTED IN THE GAS
 FIXTURE LOAD SUMMARY. CLARIFY.
 6) THE GAS RISER DOES NOT SHOW WHERE THE GRILLE AND THE
 FIRE PIT GAS PIPING CONNECT TO THE SYSTEM. SUBMIT A
 COMPLETE GAS RISER FOR ALL NEW AND EXISTING GAS
 APPLIANCES THAT WILL BE / ARE CONNECTED TO THIS SYSTEM.
 IF THE GRILLE AND FIRE PIT ARE CONNECTED TO A SEPARATE
 SYSTEM AND A SEPARATE METER, SUBMIT THE ENNTIRE GAS
 RISER FOR THAT SYSTEM FOR REVIEW.WPB AMEND. TO FBC
 107.2.1.
 7) SHT. P4.01 - THE PLANS NOTE THE LONGEST RUN IS 108.5
 FEET BUT I CALCULATED 214.5 FEET. IS THIS LOW PRESSURE
 OR HIGH PRESSURE? RECHECK YOUR DISTANCE. THIS WILL ALSO
 AFFECT THE SIZING.SHOW THE DISTANCE FOR THE LOW
 PRESSURE SSYSTEM FROM THE MP REGULATOR TO THE MOST
 REMOTE OUTLET ON THE SYSTEM.FGC SEC.402.4.1.
 8) SHOW THE DISTANCE FROM THE NEW REGULATOR TO THE
 FIRST TEE IN THE PIPING SYSTEM.
 9) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED
 UNDERGROUND AND ALL PIPE SIZES. GALVANIZED PIPING
 CANNOT BE INSTALLED UNDERGROUND.FGC SEC. 404.11.
 10) SHT. P4.01 REFERS TO 98UE TANKLESS WATER HEATER BUT
 THIS FIXTURE IS NOT SHOWN ON THE GAS RISER. CLARIFY.
 11) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
 12) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 KITCHEN EQUIPMENT AND ALL OTHER GAS APPLIANCES /
 EQUIPMENT PER THE 2014 FBC-FUEL GAS CODE SEC.304.1 OR
 2014 FBC-RES. SEC. G 2407.
 13) SHOW THE LOCATION OF THE TANKLESS WATER HEATER ON
 THE PLANS.WPB AMEND. TO FBC SEC. 107.2.1.
 14) THE GAS PLAN REFERS TO A 2 PSI SYSTEM AND ALSO A
 SYSTEM LESS THAN 2 PSI.THE GAS RISER DOES NOT SHOW THE
 DELINEATION OF THE TWO DIFFERENT SYSTEMS.SHOW THE
 LOCATION OF ALL MP REGULATORS, WHERE THE 2 PSI SYSTEM
 BEGINS AND ENDS AND WHERE THE LOWW PRESSURE SYSTEM
 BEGINS AND ENDS. 2014 FBC-FUEL GAS SEC.402.2 OR FBC
 RES. SEC. G2413.2.
 15) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
 16) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE.
 SECS.10.4, 10.5 OF NFPA 96-08.
 17) CLEARLY INDICATE ON THE PLAN WHAT SIZING TABLES ARE
 BBEING USED IN THIS DESIGN AND FROM WHICH CODE
 STANDARD.WPB AMEND. TO FBC SEC. 107.2.1.
 18) APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND
 SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.SUBMIT WIND LOAD ANCHORING
 DETAILS FOR THE GENERATOR.
  
 NOTE: THE PLANS ARE SO VAGUE THAT A COMPREHENSIVE
 REVIEW COULD NOT BE DONE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  