| 2016-11-21 06:12:39 | GAS REVIEW |
| | |
| | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS ON ALL GAS |
| | APPLIANCES / EQUIPMENT. EQUIPMENT SHALL BE LISTED AND |
| | LABELED PER 2014 FBC- FUEL GAS SEC.301.3. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC |
| | SEC.305.1, FBC-RES. SEC.G2408.1. |
| | 2) A SHUTOFF VALVE IS REQUIRED ON THE SUPPLY SIDE OF |
| | THE METTER. FBC- FUEL GAS SEC.409.2. |
| | 3) A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF OF EACH MP REGULATOR. FBC- FGC |
| | SEC.409.4. |
| | 4) SHT. P4.01 - NOTE #3 - THE GAS CODE IN EFFECT IS THE |
| | 2014 FBC-FUEL GAS CODE, NOT THE 2010. REVISE THE NOTE. |
| | 5) THE GRILLE AND FIRE PIT IS NOT LISTED IN THE GAS |
| | FIXTURE LOAD SUMMARY. CLARIFY. |
| | 6) THE GAS RISER DOES NOT SHOW WHERE THE GRILLE AND THE |
| | FIRE PIT GAS PIPING CONNECT TO THE SYSTEM. SUBMIT A |
| | COMPLETE GAS RISER FOR ALL NEW AND EXISTING GAS |
| | APPLIANCES THAT WILL BE / ARE CONNECTED TO THIS SYSTEM. |
| | IF THE GRILLE AND FIRE PIT ARE CONNECTED TO A SEPARATE |
| | SYSTEM AND A SEPARATE METER, SUBMIT THE ENNTIRE GAS |
| | RISER FOR THAT SYSTEM FOR REVIEW.WPB AMEND. TO FBC |
| | 107.2.1. |
| | 7) SHT. P4.01 - THE PLANS NOTE THE LONGEST RUN IS 108.5 |
| | FEET BUT I CALCULATED 214.5 FEET. IS THIS LOW PRESSURE |
| | OR HIGH PRESSURE? RECHECK YOUR DISTANCE. THIS WILL ALSO |
| | AFFECT THE SIZING.SHOW THE DISTANCE FOR THE LOW |
| | PRESSURE SSYSTEM FROM THE MP REGULATOR TO THE MOST |
| | REMOTE OUTLET ON THE SYSTEM.FGC SEC.402.4.1. |
| | 8) SHOW THE DISTANCE FROM THE NEW REGULATOR TO THE |
| | FIRST TEE IN THE PIPING SYSTEM. |
| | 9) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED |
| | UNDERGROUND AND ALL PIPE SIZES. GALVANIZED PIPING |
| | CANNOT BE INSTALLED UNDERGROUND.FGC SEC. 404.11. |
| | 10) SHT. P4.01 REFERS TO 98UE TANKLESS WATER HEATER BUT |
| | THIS FIXTURE IS NOT SHOWN ON THE GAS RISER. CLARIFY. |
| | 11) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE |
| | BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS |
| | SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. |
| | 12) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | KITCHEN EQUIPMENT AND ALL OTHER GAS APPLIANCES / |
| | EQUIPMENT PER THE 2014 FBC-FUEL GAS CODE SEC.304.1 OR |
| | 2014 FBC-RES. SEC. G 2407. |
| | 13) SHOW THE LOCATION OF THE TANKLESS WATER HEATER ON |
| | THE PLANS.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 14) THE GAS PLAN REFERS TO A 2 PSI SYSTEM AND ALSO A |
| | SYSTEM LESS THAN 2 PSI.THE GAS RISER DOES NOT SHOW THE |
| | DELINEATION OF THE TWO DIFFERENT SYSTEMS.SHOW THE |
| | LOCATION OF ALL MP REGULATORS, WHERE THE 2 PSI SYSTEM |
| | BEGINS AND ENDS AND WHERE THE LOWW PRESSURE SYSTEM |
| | BEGINS AND ENDS. 2014 FBC-FUEL GAS SEC.402.2 OR FBC |
| | RES. SEC. G2413.2. |
| | 15) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| | AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS |
| | SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426. |
| | 16) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE |
| | BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| | UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. |
| | SECS.10.4, 10.5 OF NFPA 96-08. |
| | 17) CLEARLY INDICATE ON THE PLAN WHAT SIZING TABLES ARE |
| | BBEING USED IN THIS DESIGN AND FROM WHICH CODE |
| | STANDARD.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 18) APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND |
| | SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING.SUBMIT WIND LOAD ANCHORING |
| | DETAILS FOR THE GENERATOR. |
| | |
| | NOTE: THE PLANS ARE SO VAGUE THAT A COMPREHENSIVE |
| | REVIEW COULD NOT BE DONE. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |