Plan Review Notes
Plan Review Notes For Permit 16110067
Permit Number 16110067
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-11-07 11:16:50PERMIT #16110067
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO:
 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) PER NFPA 101: 32.3.3.4.7 SMOKE ALARMS. APPROVED
 SMOKE ALARMS SHALL BE INSTALLED IN ACCORDANCE WITH
 9.6.2.10 INSIDE EVERY SLEEPING ROOM, OUTSIDE EVERY
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS, AND ON ALL LEVELS WITHIN A RESIDENT UNIT.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  