Plan Review Notes
Plan Review Notes For Permit 16110067
Permit Number 16110067
Review Stop B
Sequence Number 1
Notes
Date Text
2016-11-17 14:51:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY (FROM B TO
 I2). REVISE PLAN TO INCLUDE THIS INFORMATION. SEE FBC
 EB CHAPTER 10. (SHEET LS1.1 STATES THIS IS A CHANGE OF
 USE. )
  
 2. LS1.1 INCLUDES A STATEMENT THAT BUILDING IS TO BE
 FULLY SPRINKLERED, SEE FIRE SPRINKLER DRAWINGS UNDER
 SEPARATE SUBMITTAL.
  
 IS THE BUILDING CURRENTLY SPRINKLERED? NOTES ON THE
 PLAN APPEAR TO INDICATE THAT SPRINKLERS ARE PROPOSED.
 IT APPEARS THAT THIS IS A LEVEL 3 ALTERATION, AND FIRE
 SPRINKLERS APPEAR TO BE REQUIRED FBC 5TH EDITION
 EXISTING BUILDING 804.2.4.
  
 IF SPRINKLERS ARE PROPOSED, PROVIDE FIRE SPRINKLER
 DESIGN DOCUMENTS AS REQUIRED BY FBC 107.3.5 (5). IS THE
 EXISTING WATER SERVICE ADEQUATE FOR A NEW SPRINKLER
 SYSTEM, OR WILL A NEW UNDERGROUND LINE BE REQUIRED?
  
 3. ENERGY CALC INPUT DATA LACKS DOORS, PLAN SHOWS A
 STEEL DOOR, PLEASE CORRELATE FBC 107.
  
 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB,
 INCLUDING A COST BREAKDOWN, FBC 109.
  
 5. SEE ROOF REVIEW. THE INFORMATION REQUIRED TO OBTAIN
 A ROOF SUB PERMIT MAY BE DEFERRED UPON REQUEST.
  
 6. SHEET A2.1 SPECS R19, 3.5 INCH INSULATION FOR THE
 ROOF. THE ENERGY CALCS SPEC 6 INCH INSULATION, R20.
 PLEASE CORRELATE.
  
 7. SHEET S4 SHOWS EXISTING ROOF TO REMAIN, LIGHTWEIGHT
 CONCRETE. THE ENERGY CALCS DO NOT INCLUDE TWO DIFFERENT
 ROOF ASSEMBLIES, CLARIFY. THE PERMIT WILL BE ISSUED
 WITH PROVISO THAT THE EXISTING ROOF IS NOT INCLUDED IN
 THE SCOPE OF THIS PERMIT.
  
 8. THE FOLLOWING PRODUCT APPROVALS WERE SUBMITTED AND
 FOUND ACCEPTABLE:
 JOHNS MANVILLE BUILT UP ROOF OVER CONCRETE DECK
 PGT SS 3500 ALUMINUM STOREFRONT SYSTEM
 PGT SE 3550 ALUMINUM STOREFRONT ENTRANCE DOOR
  
 THIS PERMIT WILL BE ISSUED WITH PROVISO: PRODUCT
 APPROVALS FOR COMPONENTS AND CLADDING WHICH ARE
 REQUIRED BUT NOT SUBMITTED AND REVIEWED PRIOR TO PERMIT
 ISSUANCE (FOR INSTANCE, THE BILCO ROOF HATCH, THE STEEL
 EXTERIOR DOOR) ARE REQUIRED TO BE SUBMITTED AND
 REVIEWED AS A REVISION PRIOR TO INSTALLATION.
  
 9. THIS PERMIT WILL BE ISSUED WITH PROVISO, SEPARATE
 PERMITS REQUIRED FOR SIGNS, MONUMENT SIGNS, DUMPSTER
 ENCLOSURE, FENCING, SITE LIGHTING,
  
 10. THIS PERMIT WILL BE ISSUED WITH PROVISO, SITE
 LIGHTING IS REQUIRED TO COMPLY WITH FBC 1006 (MEANS OF
 EGRESS ILLUMINATION).
  
 11. FBC 1004.1.2, CLARIFY OCCUPANT LOAD FOR THE
 RESIDENTIAL AREA. THE OCCUPANT LOAD IS LESS THAN THE
 NUMBER OF BEDS SHOWN, AND SP1 STATES THERE ARE 46 BEDS.
 IT APPEARS THAT DESIGN OCCUPANT LOAD IS HIGHER THAN THE
 TABLE, CLARIFY OR REVISE.
  
 12. A1.1 NOTE 4 STATES THAT KITCHEN DESIGN AND
 EQUIPMENT ARE ATTACHED, UNABLE TO LOCATE INFORMATION.
 WHO WILL USE THE KITCHEN, RESIDENTS OR STAFF? IS THIS A
 WORK AREA, OR AN AMENITY? SEE ALSO FBC B 904.2.1, FBC
 ACCESSIBILITY. IT APPEARS THAT THIS WILL SERVE AS A
 COMMERCIAL KITCHEN (STAFF ONLY); REVISE PLAN TO
 CLARIFY.
  
 13. A7.3, DETAIL 5 IS FOR A SMOKE BARRIER, CLARIFY.
 OTHER SHEETS REFER TO A SMOKE PARTION WHICH IS REQUIRED
 BY FBC 407.3. IT IS ACCEPTABLE TO EXCEED CODE
 COMPLIANCE BUT, IF IT IS CALLED A SMOKE BARRIER, THE
 REQUIREMENTS OF A SMOKE BARRIER ARE APPLICABLE.
  
 14. DOOR SCHEDULE, A7.1, REVISE TO INCLUDE REQUIREMENTS
 FOR DOORS, FBC 407.3.1.
  
 15. A6.1, OR OTHER APPLICABLE SHEET, REVISE PLAN TO
 INCLUDE REQUIREMENT THAT THE CEILING IS TO BE INSTALLED
 IN A MANNER TO LIMIT THE TRANSFER OF SMOKE, FBC 7F10.4.
  
 16. THIS PERMIT WILL BE ISSUED WITH PROVISO, A SEPARATE
 PERMIT IS REQUIRED FOR THE GENERATOR REFERENCED ON
 E4.0.
  
 17. A NOTE ON SHEET LS1.1 STATES THAT THE FIRE ALARM IS
 EXISTING AND FULLY FUNCTIONAL. A FIRE ALARM SYSTEM IN
 ACCORDANCE WITH FBC B 907.2.6 IS REQUIRED. SINCE THE
 ENTIRE SPACE IS BEING RECONFIGURED, IT APPEARS THAT AN
 ALTERATION OF THE FIRE ALARM SYSTEM IS REQUIRED.
 COMPLIANCE WITH OTHER REQUIREMENTS, SUCH AS OCCUPANT
 NOTIFICATION SYSTEM, IS NOT CLEAR AS THIS WAS NOT
 REQUIRED FOR THE BUSINESS OCCUPANCY. ARE OCCUPANT
 NOTIFICATION REQUIREMENTS THE SAME FOR BUSINESS AS
 SLEEPING AREAS? REVISE PLAN TO NOTE BASIC DESIGN
 REQUIREMENTS. A SEPARATE PERMIT IS REQUIRED FOR THE
 FIRE ALARM AND A COMPLETE REVIEW WILL BE DONE AT THAT
 TIME.
  
 18. A8.1, DETAILS 2, 5 GRAB BAR IS TOO HIGH, SEE FBC A
 609.9, TOP CANNOT EXCEED 36 IN.
  
 19. PROVIDE DETAILS FOR THE SHOWERS, FBC A 608.
  
 20. A8.1, THE BOTTOM OF THE REFLECTIVE SURFACE IS TO BE
 40IN ABOVE THE FINISHED FLOOR, FBC A 603.3.
  
 19. PROVIDE A GEOTECHNICAL REPORT, FBC 1803.2.
 STRUCTURAL ENGINEER IS TO REVIEW THE REPORT PRIOR TO
 RESUBMITTAL.
  
 20. PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY, FBC
 107. THE SURVEY SHOULD INCLUDE ALL GRADE LEVEL
 MECHANICAL EQUIPMENT LOCATED OUTSIDE OF THE BUILDING.
  
 21. THIS PARCEL IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (120229 0015B, FLOOD ZONE A8, BFE 16'). REVISE THE
 PLAN TO SHOW THE EXISTING FLOOR ELEVATION, PROPOSED
 FLOOR ELEVATION, AND ELEVATION OF ALL PROPOSED
 EQUIPMENT. THE MINIMUM DFE REQUIRED (BFE 16' + 1'
 FREEBOARD CITY OF WEST PALM BEACH MUNICIPAL CODE 94-541
 THROUGH 94-547). SEE ALSO NFIP REVIEW.
  
 22. INFORMATION REGARDING THE TOTAL VALUE OF THE
 PROJECT IS REQUIRED AT THIS TIME. IF IT IS AGREED THAT
 ITEMS SUCH AS FIRE SPRINKLER AND FIRE ALARM MAY BE
 SUBMITTED LATER, THE VALUE OF SUCH ITEMS IS REQUIRED AT
 THIS TIME SO THAT A SUBSTANTIAL IMPROVEMENT
 DETERMINATION CAN BE MADE, FBC 1612.
  
 23. A COMPLETE REVIEW CANNOT BE DONE AT THIS TIME UNTIL
 THE INFORMATION REGARDING VALUE AND EXISTING BUILDING
 ELEVATION IS PROVIDED. PLEASE PROVIDE THIS INFORMATION
 VIA EMAIL. IF AN ELEVATION CERTIFICATE IS AVAILABLE,
 SEND VIA EMAIL.
  
  
  
  
  
  
  