| 2018-04-05 16:50:35 | MECHANICAL PROVISO. |
| | 4/5/18 |
| | |
| | REQUIRED SUBMITTALS: |
| | |
| | 1) WIND LOAD ENGINEERING FOR INSTALLATION OF ALL |
| | EXTERIOR MECHANICAL EQUIPMENT INCLUDING AC CONDENSERS |
| | AND FANS. |
| | |
| | 2) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S |
| | FOR CONDENSER ANCHORING CLIPS, EXHAUST AND OUTDOOR AIR |
| | LOUVERS. |
| | |
| | 3) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | INSTRUCTIONS FOR THE GARAGE EXHAUST FANS, THE HONEYWELL |
| | GAS MONITORS AND CONTROLLER, THE EXHAUST DUCT |
| | FIREWRAPPING, FIRE DAMPERS, AND SMOKE DETECTORS. |
| | |
| | ALL SUBMITTALS SHALL BE REVIEWED AND APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD AND BEAR SHOP DRAWING |
| | APPROVAL STAMPS. |
| | |
| | 1) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THEAPPLICATION AND THAT |
| | ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | 2) DEFERRED SUBMITTAL. 2017 FBC 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |