| 2018-02-09 14:01:56 | 3RD REVIEW FBC-2014 MECHANICAL , ENERGY CONSERVATION |
| | CODES. |
| | WEST PALM BEACH AMENDMENTS TO THE FBC. |
| | PERMIT #16110061 |
| | 7/7/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE VENTILATION SYSTEM IN THE GOLF CART PARKING |
| | GARAGE WHERE THE BATTERIES ARE CHARGED IS STILL IN |
| | QUESTION. THE SUBMITTAL FROM CLUB CAR AND THE REVISED |
| | PLAN ARE NOT CLEARLY INDICATING THAT THE SYSTEM WILL |
| | PROVIDE CONTINUOUS VENTILATION THAT WILL LIMIT THE |
| | CONCENTRATION OF HYDROGEN TO 1.0 PERCENT OF THE VOLUME |
| | OF THE ROOM- SECTION 502.4.1. PROVIDE FURTHER EVIDENCE |
| | AND CALCULATIONS |
| | |
| | ACCORDINGLY. PLEASE NOTE THAT THE SENSORS SHALL ALSO BE |
| | CAPABLE OF DETECTING NO2 IN CONJUNCTION WITH CO2 PER |
| | SECTION 404.1 (2). |
| | |
| | 2) REFER TO SECTIONS 510.6.1 & 510.6.2: THE FIRE |
| | DAMPERS IN THE GARAGE EXHAUST DUCTS ARE PROHIBITED, AND |
| | THE DUCTS SHALL BE ENCLOSED IN FIRE-RESISTANT SHAFT |
| | CONSTRUCTION WHERE THEY PENETRATE THE FLOOR/CEILING |
| | SASSEMBLY, ASCEND UP THROUGH THE 1ST FLOOR AND ATTIC |
| | SPACE TO TERMINATION ABOVE THE ROOF. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |