| 2017-07-07 11:30:41 | 2ND REVIEW FBC-2014 MECHANICAL , ENERGY CONSERVATION |
| | CODES. |
| | WEST PALM BEACH AMENDMENTS TO THE FBC. |
| | PERMIT #16110061 |
| | 7/7/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M0.1 & M1.1: REFER TO COMMENT #3 FROM THE 1ST |
| | REVIEW AND SECTION 404.2 MINIMUM VENTILATION FOR |
| | PARKING GARAGES. PLEASE PROVIDE EXHAUST CACULATIONS |
| | BASED ON A MINIMUM AIRFLOW RATE OF 0.05 CFMS PER SQ. |
| | FT. AND A MAXIMUM CAPABILITY OF 0.75 CFMS PER SQ. FT. |
| | PLACE A NOTE THAT THE SYSTEM WILL OPERATE CONTINUOUSLY |
| | NOT BELOW THE MINIMUM AIRFLOW RATE. |
| | |
| | 2) M1.1, DETAIL 2: PLEASE PROVIDE A WRITTEN NARRATIVE |
| | TO ACCOMPANY AND CLARIFY THE GAS MONITORING CONTROL |
| | SEQUENCE OF OPERATION. |
| | |
| | 3) M1.1: REFER TO COMMENT #9 FROM THE 1ST REVIEW AND |
| | SECTIONS 502.4 & 502.8. AS PREVIOUSLY REQUESTED |
| | INDICATE WHERE THE GOLF CART BATTERIES WILL BE STORED |
| | AND CHARGED AND PROVIDE CONTINOUS VENTILATION THAT WILL |
| | LIMIT THE CONCENTRATION OF HYDROGEN TO 1.0 PERCENT OF |
| | THE TOTAL VOLUME OF THE ROOM- SECTION 502.4.1. A) THE |
| | SUBMITTED DOCUMENT FROM "CLUB CAR" APPEARS TO BE JUST |
| | ONE PAGE OF A MULTI-PAGE DOCUMENT. PLEASE PROVIDE A |
| | COMPLETE SUBMITTAL WITH A REVIEW AND APPROVAL STAMP BY |
| | THE ENGINEER OF RECORD. B) THE FLOOR PLAN SHOWS ONLY |
| | TWO GAS SENSORS FOR THE ENTIRE AREA: PROVIDE |
| | MANUFACTURER'S SPECIFICATIONS TO VERIFY THE SPACINGS |
| | ARE ADEQUATE, AND NOTE THAT A SENSOR WILL BE REQUIRED |
| | IN THE BATTERY STORAGE ROOM. C) PLEASE PLACE A NOTE ON |
| | THE PLANS PURSUANT TO TABLE 403.3 FOOTNOTE B THAT NO |
| | EXHAUST AIR FROM THE PARKING GARAGE WILL BE |
| | RECIRCULATED TO OCCUPIED SPACES VIA AHU-1. |
| | |
| | 4) M1.1, M1.2, & M2.1- DETAIL 12: PROVIDE DUCT SMOKE |
| | DETECTORS IN THE RETURN AIR SYSTEMS OF AHU'S 1, 2, & 3- |
| | SECTION 606.2.1. PROVIDE SYMBOLS TO SHOW THE |
| | INSTALLATION LOCATIONS. |
| | |
| | 5) M1.2 & M1.3 & M1.3: NO REFERENCE TO THE MUA FAN(S) |
| | FOR THE HOODS ARE SHOWN ON THE MECHANICAL FLOOR PLANS |
| | AND NO EQUIPMENT SCHEDULES HAVE BEEN PROVIDED, OR FAN |
| | LOCATIONS SHOWN. |
| | |
| | 6) M1.2: THE 2X2' ACCESS PANEL FOR AHU-2 APPEARS TWO |
| | SMALL TO BE ABLE TO REMOVE AND REPLACE AHU-2, AND NO |
| | PANEL LOCATIONS ARE SHOWN FOR VAV BOXES AND FANS THAT |
| | ARE LOCATED ABOVE HARD CEILINGS- PLEASE SEE CODED NOTE |
| | #1 ON THE PLAN, AND SECTION 306.1 AND SHOW ALL PROPOSED |
| | PANEL LOCATIONS AND DIMENSIONS. |
| | |
| | 7) M1.1: PROVIDE THE CLEARANCE DISTANCE MEASUREMENT |
| | BETWEEN EXHAUST FANS EF-3A & 3B AND THE 24X12 O/A |
| | LOUVER. THE LOCATIONS DO NOT APPEAR TO BE IN COMPLIANCE |
| | WITH EITHER 401.4 OR 506.3.13.3. |
| | |
| | 8) M2.1 : PROVIDE THE WIND DESIGN CRITERIA USED TO |
| | ESTABLISH THE TIE DOWN DESIGN FOR THE CONDENSERS, AND |
| | SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE |
| | CLIP. PLEASE NOTE ALL SUBMITTALS SHALL BEAR THE SHOP |
| | DRAWING APPROVAL STAMP FROM THE EOR. |
| | |
| | 9) PLEASE PROVIDE A MECHANICAL ROOF PLAN SHOWING THE |
| | LOCATIONS OF OF EQUIPMENT, AND ALL MECHANICAL OR |
| | GRAVITY O/A INTAKE OPENINGS AND EXHAUST OUTLETS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |