| 2017-02-03 10:35:57 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16110061 |
| | 2/3/17 |
| | |
| | 1) THE SUMMARY AC COOLING AND HEATING CALCULATIONS |
| | SHALL BEAR AN ELECTRONIC SIGNATURE AND SEAL BY THE |
| | ENGINEER OF RECORD- SECTION C403.2.1 EXCEPTION FBC-14 |
| | ENERGY CONSERVATION, AND SECTION 61G15-23.005 FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 2) THE ENERGYGAUGE COMPLIANCE SUBMITTAL MUST BEAR THE |
| | CERTIFICATION SIGNATURES OF THE DESIGN PROFESSIONALS |
| | AND THE OWNER/AGENT ON PAGE 3, AND MUST BE |
| | ELECTRONICALLY SIGNED AND SEALED PER SECTION |
| | 61G15-23.005 FAC. |
| | |
| | 3) PROVIDE EXHAUST VENTILATION CALULATIONS FOR THE |
| | PARKING GARAGE, THE LOCKER ROOMS AND BATHROOMS, AND THE |
| | KITCHEN PER TABLE 403.3. A) INDICATE HOW MAKEUP AIR IS |
| | BEING PROVIDED FOR THE GARAGE AND LOCKER ROOM EXHAUST |
| | SYSTEMS. B) PROVIDE AIR BALANCE CALCULATIONS FOR BOTH |
| | FLOORS THAT INCLUDE ALL EXHAUST SYSTEMS. |
| | |
| | 4) ADVISORY: SEPARATE PERMITS AND PLANS ARE REQUIRED |
| | FOR THE KITCHEN EXHAUST SYSTEM, THE KITCHEN HOOD FIRE |
| | SUPPRESSION, AND THE WALK-IN COOLER/FREEZER. PLEASE |
| | PLACE A NOTE ON THE PLANS ACCORDINGLY. PLEASE NOTE THE |
| | FOLLOWING: A) THE HOOD EXHAUST FAN OUTLETS TERMINATING |
| | AT THE EXTERIOR WALL SHALL BE IN COMPLIANCE WITH |
| | 506.3.13.2. B) THE FANS MUST BE ANCHORED TO THE |
| | BUILDING TO WITHSTAND THE DESIGN WINDLOADS AND |
| | PRESSURES, AND INSTALLED IN A MANNER TO PREVENT WATER |
| | INTRUSION. |
| | |
| | 5) THE AC EQUIPMENT SCHEDULE ON M-3.1 INDICATES THAT AN |
| | ERV IS REQUIRED FOR AHU-1: REFER TO TABLE C403.2.6 AND |
| | SECTION C403.2.6 FBC-14 ENERGY CONSERVATION. |
| | |
| | 6) M-3.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE VAV |
| | BOXES. |
| | |
| | 7) M-3.1: PROVIDE CONTROL SEQUENCES FOR ALL EXHAUST |
| | SYSTEMS. |
| | |
| | 8) M-1.1: LABEL THE AIR HANDLER, IDENTIFY AND LABEL THE |
| | SUPPLY DIFFUSERS AND RETURN GRILLS. |
| | |
| | 9) M-1.1: PROVIDE VENTILATION FOR THE BAG STORAGE, |
| | STORAGE, AND MAINTENANCE ROOMS- TABLE 403.3. PLEASE SEE |
| | SECTION 502 AND ALL APPLICABLE SUB-SECTIONS AND PROVIDE |
| | EXHAUST VENTILATION WHERE REQUIRED FOR ALL FUEL, OR |
| | BATTERY STORAGE ROOMS OR AREAS. PLEASE NOTE THAT A |
| | DETAILED LIST OF ALL HAZARDOUS MATERIALS AND THEIR |
| | QUANTITIES MAY BE REQUIRED PER SECTION414.1.3 FBC-14 |
| | BUILDING. |
| | |
| | 10) M-1.1 & M-1.2: FIRE DAMPERS ARE REQUIRED WHERE THE |
| | 32X20, 22X14, AND 3" DUCTS PENETRATE THE FLOOR/CEILING |
| | ASSEMBLY- SECTION 607.6.2. |
| | |
| | 11) M-1.1 & M-1.2: THE PLANS ARE INDICATING AIR FROM |
| | THE GROUND FLOOR GARAGE WILL BE RECIRCULATED INTO THE |
| | OCCUPIED AREAS ON THE FIRST FLOOR WHICH IS PROHIBITED |
| | BY FOOTNOTE B, TABLE 403.3. |
| | |
| | 12) M-1.1: PROVIDE THE EXHAUST OUTLET CLEARANCE |
| | DISTANCES AS OUTLINED IN SECTION 501.3.1. |
| | |
| | 13) M.1-1: CORRECT THE DUCT HEIGHT NOTE TO INDICATE |
| | MINIMUM 7'0" CLEARANCE FROM FINISHED GARAGE FLOOR TO |
| | BOTTOM OF THE DUCT- SECTION 406.4.1 FBC-14 BUILDING. |
| | |
| | 14) M-1.2: THE PLAN DOES NOT APPEAR TO SHOW ANY EXHAUST |
| | VENTILATION FOR THE MEN'S AND WOMEN'S LOCKER ROOMS |
| | WHICH IS REQUIRED BY TABLE 403.3. PLEASE SEE FOOTNOTE G |
| | AS IT APPEARS RECIRCULATION FROM THOSE AREAS IS |
| | EXCEEDING THE ALLOWABLE MAXIMUM. |
| | |
| | 15) M-1.2: THE PLAN APPEARS TO SHOW TWO L4 DIFFUSERS IN |
| | THE RECEPTION ROOM CONNECTED TO TWO B RETURN GRILLS IN |
| | THE GOLF-PRO OFFICE. |
| | |
| | 16) M-1.2: PROVIDE ALL FLEX DUCT SIZES. |
| | |
| | 17) M-1.2: INDICATE HOW ACCESS WILL BE PROVIDED FOR |
| | MAINTENANCE AND REPLACEMENT OF AHU'S 2 & 3- SECTION |
| | 306.1. |
| | |
| | 18) M-1.2: PROVIDE ENGINEERED DETAILS FOR TIE DOWN OF |
| | THE AC CONDENSER UNITS- SECTION 301.15. |
| | |
| | 19) SUBMIT TWO COPIES OF A VALID FL.PRODUCT APPROVAL |
| | AND/OR MIAMI-DADE NOA FOR THE LOUVERS- RULE 9N-B FAC. |
| | |
| | 20) A COMPLETE REVIEW OF THE PROPOSED PROJECT CANNOT BE |
| | PERFORMED AT THIS TIME DUE TO A LACK OF INFORMATION. IN |
| | ORDER TO EXPEDITE THE SECOND REVIEW PLEASE PROVIDED A |
| | DETAILED NARRATIVE THAT ITEMIZES ALL CORRECTIONS MADE |
| | TO THE PLANS. PLEASE NOTE ADDITIONAL COMMENTS MAY |
| | FOLLOW THIS INITIAL REVIEW. |
| | |