2017-11-16 15:52:43PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS.
 THE ENERGY COMPLIANCE FORMS AND THE EQUIPMENT SCHEDULE
 ON THE MECHANICAL PLANS ARE REQUIRED TO MATCH THE
 EQUIPMENT SIZING CALCULATIONS. FBC ENERGY CONSERVATION
 - SECT. 403.6.1 EQUIPMENT SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED IN ACCORDANCE WITH ACCA MANUAL
 S BASED ON THE EQUIPMENT LOADS CALCULATED IN ACCORDANCE
 WITH MANUAL J OR OTHER APPROVED HEATING AND COOLING
 CALCULATION METHODOLOGIES, BASED ON BUILDING LOADS FOR
 THE DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION 302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT
 INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS. (ONLY ONE SET WAS SUBMITTED. SUBMIT AN
 ADDITIONAL SET OF SIZING CALCULATIONS.)
  
 2) THE EQUIPMENT SIZING CALCULATIONS, INDICATE 10
 PEOPLE. THIS IS TOO MANY PEOPLE FOR A THREE BEDROOM
 RESIDENCE. PLEASE CORRECT.
  
  
  