| Date |
Text |
| 2017-11-16 15:52:43 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY MECHANICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS. |
| | THE ENERGY COMPLIANCE FORMS AND THE EQUIPMENT SCHEDULE |
| | ON THE MECHANICAL PLANS ARE REQUIRED TO MATCH THE |
| | EQUIPMENT SIZING CALCULATIONS. FBC ENERGY CONSERVATION |
| | - SECT. 403.6.1 EQUIPMENT SIZING. HEATING AND COOLING |
| | EQUIPMENT SHALL BE SIZED IN ACCORDANCE WITH ACCA MANUAL |
| | S BASED ON THE EQUIPMENT LOADS CALCULATED IN ACCORDANCE |
| | WITH MANUAL J OR OTHER APPROVED HEATING AND COOLING |
| | CALCULATION METHODOLOGIES, BASED ON BUILDING LOADS FOR |
| | THE DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| | CONDITIONS DESCRIBED IN SECTION 302.1. THIS CODE DOES |
| | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR |
| | FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT |
| | EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT |
| | INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL |
| | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM |
| | EXHAUST SYSTEMS. (ONLY ONE SET WAS SUBMITTED. SUBMIT AN |
| | ADDITIONAL SET OF SIZING CALCULATIONS.) |
| | |
| | 2) THE EQUIPMENT SIZING CALCULATIONS, INDICATE 10 |
| | PEOPLE. THIS IS TOO MANY PEOPLE FOR A THREE BEDROOM |
| | RESIDENCE. PLEASE CORRECT. |
| | |
| | |
| | |