Plan Review Notes
Plan Review Notes For Permit 16110027
Permit Number 16110027
Review Stop E
Sequence Number 1
Notes
Date Text
2016-11-09 14:39:24REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO"S
  
 1] ADD AN INTERSYSTEM BONDING TERMINAL TO THE RISER
 DIAGRAM GROUNDING DETAIL. NEC 250.94
  
 2] FBC-R SECTION 315.1 CO/ALARM REQUIRED BECAUSE OF AN
 ATTACHED GARAGE WITHIN 10? OF A SLEEPING ROOM.
  
  
  