2016-12-02 19:07:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R315.1 CARBON MONOXIDE PROTECTION. EVERY
 SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
  
 2) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC.
 THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE
 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT
 DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC
 FIFTH EDITION. FOR EXAMPLE THE GENERAL NOTE ON SHEET
 S-4.
  
 3) THE FOOTING NOTES ON S-3 FOR WALL SECTION 2 ARE NOT
 CONSITENT WITH THE FOUNDATION SCHEDULE ON S-1. PLEASE
 CORRECT. FBC-R404.1.6 HEIGHT ABOVE FINISHED GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE. FOOTINGS AT EXTERIOR WALLS ARE REQUIRED TO
 BE 12 INCHES BELOW GRADE PER FBC R403.1.4.
  
 4) FBC R301.2.1 WIND DESIGN CRITERIA. SPECIFY THE
 EXPOSURE CATEGORY AND THE COMPONENT AND CLADDING
 PRESSURES ON THE PLANS.
  
 5) THE KITCHEN WINDOW IS NOT SHOWN ON THE SOUTH
 ELEVATION ON SHEET A-2 OR ON SHEETS S-1, S-2, M-1, E-1
 OR WP-1. FBC 107.2.1
  
 6) THE WINDOW AND DOOR ID TAG LETTERS AND NUMBERS ON
 THE ELEVATIONS DO NOT MATCH THE SCHEDULES ON SHEETS A-1
 AND A-2. FBC 107.2.1
  
 7) THE WOOD BEAM FOR THE FRONT PORCH IS SPECIFIED AS
 (3) 2 X 8S ON S-2 AND (2) 2 X 8S ON S-3. FBC 107.2.1
  
 8) THE ROOF FASTENING SPECIFIED ON S-2 IS NOT
 CONSISTENT WITH THE NOTE ON WALL SECTION 2 ON S-3. FBC
 107.2.1
  
 9) ON SHEET S-2 THE LINTEL ID TAGS PC 1, PC 2, ETC. DO
 NOT HAVE A CORRESPONDING LINTEL SCHEDULE. FBC 107.2.1
  
 10) SOME OF THE OPENINGS ARE MISSING THE LINTEL ID
 TAGS. FBC 107.2.1
  
 11) THE DOOR SCHEDULE SPECIFIES THE EXTERIOR DOORS AS
 WOOD AND THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE
 FOR METAL DOORS. DCA RULE 9N-3
  
 12) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE ASPHALT ROOF SHINGLES AND THE SLIDING GLASS DOORS.
  
 13) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  