| Plan Review Notes For Permit 16110022 |
| Permit Number |
16110022 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-03 10:57:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) A FLOOR PLAN INDICATING WHICH 5 DOORS AND THEIR | | | LOCATIONS WAS NOT PROVIDED. | | | | | | PLEASE PROVIDE A FLOOR PALN INDICATING THE PROPOSED | | | DOORS. | | | | | | | | | | | | 2) ELECTRICAL WIRING DETAILS NOT PROVIDED. | | | | | | PLEASE PROVIDE POWER SOURCE AND WIRING DETAILS. | | | | | | | | | 3) THERE IS NO INDICATION OF AN EXISITNG FIRE ALARM AND | | | IF ANY DOORS WILL BE TIED - IN TO IT. | | | | | | PLEASE PROVIDE THE APPLICANLE NOTE. | | | | | | ANY TIE - IN TO THE FIRE ALARM SHALL BE DONE BY | | | CERITIFIED LIFE SAFETY CONTRACTORS UNDER SEPARATE SHOP | | | DRAWINGS. | | | | | | | | | | | | 4) PLEASE PROVIDE DETAILS ON EXITING OUT EACH DOOR. | | | EGRESS SHALL NOT BE IMPAIRED AND SHALL COMPLY WITH NFPA | | | 101, CHAPTER 7, MEANS OF EGRESS. | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|