| 2016-11-17 08:47:31 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL, EXISTING |
| | BUILDING |
| | |
| | WORK ORIGINALLY APPLIED FOR ON 02/28/2005 AND IS |
| | DOCUMENTED AS COMPLETE ON 03/09/2005, BUT WITH NO |
| | APPROVED INSPECTION HISTORY. |
| | |
| | REVIEW FOR RE-ISSUANCE OF PERMIT NUMBER 05021507 FOR |
| | FLAT AND SLOPED RE-ROOFING OF WORK THAT WAS COMPLETED |
| | IN 2005. THERE IS NO APPROVED INSPECTION HISTORY. THE |
| | OWNER HAS ENGAGE A LICENSED ROOFING CONTRACTOR. THE |
| | CONTRACTOR AND OWNER MUST ENGAGE A LICENSED ENGINEER OR |
| | ROOFING CONSULTANT TO PERFORM AN INVESTIGATION AND/OR |
| | TESTS TO ASSURE ALL THE REQUIREMENT OF THE PERMIT WERE |
| | SATISFACTORILY COMPLETED. PURSUANT TO FBC 110.3.9.1 AND |
| | FBC 117, A WRITTEN REPORT WITH PHOTOGRAPHIC EVIDENCE IS |
| | REQUIRED. SUCH REPORT SHALL INCLUDE BUT NOT BE LIMITED |
| | TO CERTIFYING THE FOLLOWING INSPECTIONS. |
| | |
| | ROOF SHEATHING RE-NAILING |
| | UNDERLAYMENT AND UNDERLAYMENT FASTENER SPACING |
| | INCLUDING ALL METAL AND DRIP EDGE INSTALLATION. |
| | ROOFING MATERIAL INSTALLATION, AND FINAL. |
| | THE REMAINING USEFUL LIFE OF THE ROOF COVERING SHALL BE |
| | ESTIMATED AND DOCUMENTED IN THE REPORT. . |
| | |
| | FBC 110.3.9.1 AFFIDAVIT FOR INSPECTION. WITH SPECIFIC |
| | PRIOR APPROVAL OF, AND IN A FORMAT |
| | ACCEPTABLE TO THE BUILDING OFFICIAL, AN AFFIDAVIT FOR |
| | CERTIFICATION OF INSPECTION MAY BE |
| | ACCEPTED FROM THE PERMIT QUALIFIER; WHEN ACCOMPANIED BY |
| | EXTENSIVE PHOTOGRAPHIC |
| | EVIDENCE OF SUFFICIENT DETAIL TO DEMONSTRATE CODE |
| | COMPLIANCE. |
| | |
| | FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR |
| | TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE |
| | TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN |
| | APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. |
| | |
| | DEPENDING ON THE ACCEPTABILITY OF THE REPORT AND |
| | INSPECTION AFFIDAVIT, THE MATTER MAY BE RESOLVED |
| | WITHOUT FURTHER NEED TO SCHEDULE ANY INSPECTION. PLEASE |
| | COORDINATE WITH ME DIRECTLY UPON FURTHER SUBMITTAL. |
| | |
| | ALTERNATIVELY, A RE-SUBMITTAL MAY BE ACCEPTED UNDER |
| | THIS PERMIT RECORD FOR A NEW ROOFING SYSTEM. ADDITIONAL |
| | REVIEW AND FEES WILL APPLY. |
| | |