| Plan Review Notes For Permit 16110007 |
| Permit Number |
16110007 |
|
| Review Stop |
THRESHOLD |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-16 14:16:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. CLARIFY; DOES APPLICANT CONSIDER THIS A THRESHOLD | | | BUILDING, FS552.79? IF YES, HAVE ENGINEER ADD THE | | | STATEMENT REQUIRED BY FS 553.79(7)(D) AND PROVIDE A | | | THRESHOLD INSPECTION PLAN. | | | | | | 2. IF IT IS AGREED THAT THIS IS A THRESHOLD PROJECT, | | | COMPLETE THE SPECIAL INSPECTOR AGREEMENT. THIS WAS SENT | | | VIA EMAIL TO [email protected]. | | | | | | 3. PROVIDE RESUMES FOR THE CONTRACTOR, INSPECTORS, SI, | | | AND SI FIRM. | | | | | | 4. THRESHOLD DOCUMENTS MAY BE SENT VIA EMAIL FOR | | | PRELIMINARY REVIEW. | | | | | | 5. IF APPLICANT DISAGREES THAT THIS IS THRESHOLD, | | | PLEASE CONTACT ME TO DISCUSS. A RESIDENT INSPECTOR MAY | | | BE REQUIRED DEPENDING ON APPLICANT'S SCHEDULE AND THE | | | BUILDING DEPARTMENT'S ABILITY TO COMPLETE INSPECTIONS | | | TO MAINTAIN THE SCHEDULE. ALL OF THE SAME INFORMATION | | | IS REQUIRED FOR A RESIDENT INSPECTOR PROJECT, BUT THE | | | RESIDENT INSPECTOR AGREEMENT IS TO BE COMPLETED. | | | | | | |
|