| 2016-11-07 11:27:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) ALL LIFE SAFETY SHEETS - UNDER THE LIFE SAFETY |
| | GENERAL NOTES IT INDICATES "NO DEVICES OR EXIT OPENINGS |
| | ARE ALTERED BY THIS PROJECT." HOWEVER, THERE ARE AD |
| | SHEETS INDICATING SPECIFIC EXITS DOORS BEING REPLACED |
| | WITH BLOCKED EXIT SIGNS AND REROUTING. |
| | |
| | PLEASE CLARIFY AND/OR CORRECT WITH AN APPLICABLE NOTE. |
| | |
| | |
| | |
| | 2) SHEETS AD 2.1 & 3.1 ARE NOT INDICATED WITH ANY FIRE |
| | SPRINKLER PROTECTION COMMENTS. |
| | |
| | WILL THERE BE ANY SPRINKLER HEADS AFFECTED BY THE |
| | CEILING AREA WORK? IF SO ALL WORK SHALL BE DONE BY |
| | CERITIFED LIFE SAFETY CONTRACTORS UNDER SEPARATE SHOP |
| | DRAWINGS. |
| | |
| | PLEASE CLARIFY AND/OR CORRECT WITH THE APPLICABLE NOTE. |
| | |
| | |
| | |
| | 3) SHEET A 1.0 - NOTE # 7 INDICATES THAT EXIT SIGNS AND |
| | EXIT WILL BE BLOCKED WHEN DOORS ARE REPLACED. |
| | |
| | PLEASE PROVIDE THE LIFE SAFETY PLANS TO INCLUDE THE |
| | ALTERNATE EXITS AND APPLICABLE TEMPORARY EXIT SIGNS |
| | LOCATIONS, WHEN AND WERE THE EXITS WILL BE BLOCKED. |
| | |
| | |
| | |
| | 4) SHEET A1.0 & A 7.1 - THERE ARE DOORS INDICATED AS |
| | BEING REPLACED; TG001 30.3.N, TG272 31.1.N, TG305 |
| | 31.3.N, TG013 31.3.N, TG324 1.1.N, TG055 1.1.N, AND |
| | TG049 1.1.N. ALL ARE INDICATED AS HAVING NO RATING. |
| | |
| | IT APPEARS THAT THESE DOORS ARE IN LOCATIONS THAT |
| | REQUIRE FIRE RATING. PLEASE REVIEW THE ENGINEER OF |
| | RECORD SPECS TO ENSURE THAT THEY ARE NOT REQUIRED TO BE |
| | RATED. |
| | |
| | |
| | 5) SHEET A1.0 & A 7.1 - THERE ARE THREE (3) DOORS |
| | INDICATED AS TG001 30.3.N. THE DOOR TYPES SCHEDULE, |
| | UNDER SPECIAL DOOR TYPES, INDICATES DOOR TYPE 30 AS A |
| | SLIDING DOOR. HOWEVER, TWO (2) OF THE TG001 DOORS ARE |
| | DOUBLE SWING DOORS. |
| | |
| | PLEASE REVIEW, CLARIFY AND /OR CORRECT. |
| | |
| | |
| | |
| | 6) 5) SHEET A1.0 & A 7.1 - THERE IS A DOOR SET |
| | INDICATED AS TG272 31.1.N. THE DOOR TYPES SCHEDULE, |
| | UNDER SPECIAL DOOR TYPES, INDICATES DOOR TYPE 31 AS A |
| | SLIDING DOOR. HOWEVER, THE TG272 DOOR IS A DOUBLE SWING |
| | DOOR. |
| | |
| | PLEASE REVIEW, CLARIFY AND /OR CORRECT. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |