| Notes |
| Date |
Text |
| 2016-11-04 10:12:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PERMIT VALUE IS TOO LOW. VALUE IS TO INCLUDE ALL | | | LABOR, MATERIALS, OVERHEAD, PROFIT, EVEN IF PROVIDED BY | | | OTHERS, FBC 109. | | | | | | 2. SEE FIRE COMMENTS. BUSINESS OCCUPANCY IS THE CORRECT | | | CLASSIFICATION FOR FLORIDA BUILDING CODE COMPLIANCE, SO | | | RATHER THAN CHANGE THE OCCUPANCY CLASSIFICATION PLEASE | | | ADD THE CORRECT FIRE OCCUPANCY CLASSIFICATION, FBC | | | 303.1.2. | | | | | | 3. OCCUPANT LOAD SHOULD BE DETERMINED IN ACCORDANCE | | | WITH FBC TABLE 1004.1.2 UNLESS THE SEATING IS FIXED. | | | REVISE PLAN TO STATE WHETHER THE SEATING IS FIXED OR | | | NOT, AND IF NOT, CALCULATE THE OCCUPANT LOAD AS PER THE | | | TABLE. | | | | | | 4. ACCESSIBLE SEATING AND CHECK OUT COUNTER NOT SHOWN, | | | REVISE PLAN TO PROVIDE APPLICABLE DETAILS, FBC 5TH | | | EDITION ACCESSIBILITY 226, 227, 902, 904. | | | | | | |
|