2016-11-02 13:39:08INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVIDE REVISED PANEL LOAD SCHEDULE REFLECTING NEW
 HOOD, LIGHTING AND RANGE LOADS. FBC 107.3.5
 2. PROVIDE A NOTE TO INDICATE REQUIRED TAMPER RESISTANT
 RECEPTACLE THROUGHOUT. FBC RES E4002.14
 3. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO
 INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS.
 4. ADDRESS SPACING FOR COUNTERTOP RECEPTACLES IN
 KITCHEN PER FBC RES E3901.4 TO THE RIGHT OF PENINSULA
 WHERE SINK BREAKS COUNTERTOP AREA.
 5. PROVIDE A NOTE TO PROVIDE AFCI PROTECTION PER FBC
 RES E3902.12 FOR NEW LIGHTING CIRCUITS.
 6. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  