| Plan Review Notes For Permit 16100936 |
| Permit Number |
16100936 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-11-14 17:14:46 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100936 | | | 11/14/16 | | | | | | 1) DOCUMENTATION IS REQUIRED TO VERIFY DESIGN CONDITION | | | OF 80 DEGREES AMBIENT TEMPERATURE IN THE COOKING AREA. | | | PLEASE SEE KAMM ENGINEERING PLANS AND CALCULATIONS | | | UNDER PERMIT #15090611 FOR THE MARY FISHER STUDIO. | | | OARTU-1 IS THE SYSTEM SUPPLYING CONDITIONED AIR TO THE | | | COOKING AREA. REFER TO THE ENGINEER'S CALCULATIONS FOR | | | ENTERING AND LEAVING TEMPERATURES AND THE | | | | | | SYSTEM PERFORMANCE DATA. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|