| Plan Review Notes For Permit 16100914 |
| Permit Number |
16100914 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-21 14:57:36 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING | | | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, | | | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO | | | RECORDS MANAGEMENT. PLANS ARE INLEGIBLE. | | | | | | 2] THE SCOPE OF WORK, JOB ADDRESS, & APPLICABLE CODE | | | SHALL APPEAR ON THE DRAWINGS ALONG WITH THE NAME & | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. FBC | | | 107.2.1 |
|