Plan Review Notes
Plan Review Notes For Permit 16100897
Permit Number 16100897
Review Stop E
Sequence Number 1
Notes
Date Text
2016-11-03 18:59:421ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] EVEN THOUGH MANUFACTURE SPECS WERE PROVIDED, A SITE
 SPECIFIC ONE LINE DIAGRAM SHOWING WIRE, BREAKER AND
 CONDUIT SIZE OF THE BRANCH CIRCUIT FEEDING THE BOAT
 LIFT MOTOR CONTROLLER WILL BE REQUIRED. FBC-107.
  
 2] GFCI PROTECTION IS REQUIRED IN ACCORDANCE WITH
 210.8(C). A BLOCK NOTE WILL SUFFICE.
  