| 2016-11-03 18:59:42 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] EVEN THOUGH MANUFACTURE SPECS WERE PROVIDED, A SITE | | | SPECIFIC ONE LINE DIAGRAM SHOWING WIRE, BREAKER AND | | | CONDUIT SIZE OF THE BRANCH CIRCUIT FEEDING THE BOAT | | | LIFT MOTOR CONTROLLER WILL BE REQUIRED. FBC-107. | | | | | | 2] GFCI PROTECTION IS REQUIRED IN ACCORDANCE WITH | | | 210.8(C). A BLOCK NOTE WILL SUFFICE. | | | |
|