| 2017-02-08 10:23:28 | 2ND ELECTRICAL REVIEW | | | | | | PRIOR COMMENT REGARDING FIRE ALARM SYSTEM NOT ADDRESSED | | | PER FIRE COMMENTS. | | | | | | NEW COMMENTS. | | | | | | PER NEW ELECTRICAL SERVICE SHOWN, MAIN 1 OF 6, 2 OF 6 | | | ETC MUST BE LABELED ON RISER DIAGRAM. AN AIC | | | CALCULATION WAS NOT SUBMITTED. FBC 107.3.5 | | | | | | V. PEREZ | | | *6717 |
|