| 2016-11-16 15:50:04 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. COVER SHEET IN THE SCOPE OF WORK PLEASE LIST UNDER |
| | PLUMBING ALL NEW WORK BEING DONE THE BATHROOM ADDITIONS |
| | AND LAUNDRY ADDITIONS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT. S2 WASHING MACHINE DETAIL SHOWS A 3" STANDPIPE |
| | THE RISER SHOWS A 2" STAND PIPE PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 3. SHT S1 BAR SINK NOT SHOWN ON FLOOR PLAN PLEASE |
| | PROVIDE. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. SHT S1 SHOW BATH #3 WITH A TUB ON THE RISER DIAGRAM |
| | BATH #3 IS SHOWN WITH A SHOWER PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 5. PROVIDE A RISER DIAGRAM FOR HOT AND COLD WATER. PER |
| | WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 6. WASHING MACHINES AND DRYERS SHALL COMPLY WITH FBC |
| | ACC 214 |
| | |
| | 7. THE WASHING MACHINE IN THE TWO STORY DWELLING NEEDS |
| | TO BE SHOWN ON RISER DIAGRAM. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 8. THE VALUATION OF THE JOB APPEARS TO BE A LITTLE LOW |
| | PLEASE PROVIDE A DETAILED, QUANTITY ESTIMATES, AND/OR |
| | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| | MEET THE |
| | APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL |
| | BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE |
| | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION |
| | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), |
| | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. |
| | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| | BUILDING OFFICIAL. PER WPB AMEND TO FBC 109.3 |
| | |
| | 9. PLEASE INDICATE ON THE PLAN THE WATER HEATERS TO BE |
| | EXITING TO REMAIN IN SAME LOCATION O R NEW. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 10. THE LOCATION OF FIXTURE AND APPLIANCES IN LAUNDRY |
| | ROOM DON'T MATCH FROM S1 AND E1 PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |