| Date |
Text |
| 2016-11-04 16:52:54 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) PLEASE PROVIDE THE OCCUPANCY CLASSFICATION PER THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | ONE UNIT, # 5, HAS 6 BEDROOMS, A GAME ROOM, COMMON |
| | WASHER/DRYER ROOM AND APPEARS TO HAVE A POSSIBLE USE |
| | BEYOND A SINGLE FAMILY RESIDENCE. |
| | |
| | |
| | 2) AS SUBMITTED THE CONSTRUCTION SHALL COMPLY WITH THE |
| | FLORIDA FIRE PREVENTION CODE, NFPA 101, CHAPTER 30, NEW |
| | APARTMENT BUILDINGS AND ALL APPLICABLE CODES. |
| | |
| | UNLESS OTHERWISE INDICATED SEPARATLY BY THE CORRECTION |
| | OF # 1 ABOVE, PLEASE PROVIDE AN APPLICABLE NOTE, |
| | |
| | |
| | 3) A FIRE SPRINKLER SYSTEM IS NOT INDICATED. PER NFPA |
| | 101, CHAPTER 30: |
| | |
| | 30.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| | AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| | INSTALLED IN ACCORDANCE WITH 30.3.5.2. |
| | 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| | INSTALLED, EITHER FOR TOTAL OR PARTIAL BUILDING |
| | COVERAGE, THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE |
| | WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 AND |
| | 30.3.5.4. IN BUILDINGS FOUR OR FEWER STORIES ABOVE |
| | GRADE PLANE, SYSTEMS IN ACCORDANCE WITH NFPA 13R, |
| | STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS IN |
| | LOW-RISE RESIDENTIAL OCCUPANCIES, SHALL BE PERMITTED. |
| | |
| | PLEASE PROVIDE FIRE SPRINKLER DRAWINGS OR A NARRATIVE |
| | IN COMPLIANCE WITH FS 61G - PER FLORIDA ADMINISTRATIVE |
| | CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |
| | |
| | |
| | 4) A FIRE ALARM SYSTEM IN NOT INDICATED. PER NFPA 101, |
| | CHAPTER 30 & CHAPTER 9. |
| | |
| | 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| | AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| | INSTALLED IN ACCORDANCE WITH 30.3.5.2. |
| | |
| | 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 9.6.1* GENERAL. |
| | 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY |
| | WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS |
| | CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER |
| | SYSTEM OR NEW FIRE ALARM SYSTEM IS REQUIRED BY THE |
| | FLORIDA BUILDING CODE. |
| | |
| | |
| | |
| | 5) PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED |
| | FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY |
| | MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE |
| | WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH A MALTESE CROSS SIGN MEASURING 8 INCHES |
| | HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED |
| | REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED |
| | WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. |
| | A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | |
| | |
| | 6) THE PROPOSED LAUNDRY ROOM SHALL BE PROTECTED BY 1 - |
| | HOUR SEPARATION AND FIRE SPRINKLERS |
| | |
| | PER NFPA 101, CHAPTER 30, |
| | |
| | 30.3.2 PROTECTION FROM HAZARDS. |
| | 30.3.2.1 HAZARDOUS AREAS. ANY HAZARDOUS AREA SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 8.7. |
| | 30.3.2.1.1 THE AREAS DESCRIBED IN TABLE 30.3.2.1.1 |
| | SHALL BE PROTECTED AS INDICATED. |
| | |
| | TABLE 30.3.2.1.1 LAUNDRIES 1 HOUR AND SPRINKLERS >100 |
| | FT2 (>9.3 M2) OUTSIDE OF DWELLING UNITS |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |