| 2016-11-03 18:05:54 | JOB PERMIT NUMBER: 16100893 |
| | JOB ADDRESS: 522 43RD ST |
| | WEST PALM BEACH FLORIDA |
| | DATE: NOVEMBER 3, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| | AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. |
| | |
| | 1] THE APPLICABLE CODES IN EFFECT ARE NEC 2011, NFPA 72 |
| | (2010), NFPA 101 (2012). PLEASE CORRECT NOTE 1 |
| | ACCORDINGLY. |
| | |
| | 2] SHOW CIRCUIT DESIGNATION # ON THE FLOOR PLAN TO |
| | MATCH PANEL SCHEDULE. FBC-107 |
| | |
| | 3] SHOW ALL PANELBOARDS LOCATION ON THE FLOOR PLAN TO |
| | VERIFY WORK SPACE CLEARANCES. NEC 110.26 |
| | |
| | 4] AT LEAST 1 WALL SWITCHED CONTROLLED LIGHTING OUTLET |
| | SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON THE |
| | EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH GRADE |
| | LEVEL ACCESS PER NEC 210.70(A)(2). |
| | |
| | 5] ADD GFI SYMBOL TO RECEPTACLE BY THE RANGE IN THE |
| | KITCHEN COUNTER-TOP (RED-LINED ON PLANS), ALSO ADD GFI |
| | "WP/WR" SYMBOL TO RECEPTACLE OUTLETS INSTALLED |
| | OUTDOORS. NEC 210.8(A)(6), 210.8(A)(3) &, 406.9(B). |
| | |
| | 6] ALL AREAS SPECIFIED IN NEC 210.52 SHALL HAVE AFCI |
| | PROTECTION PER NEC 210.12(A). CORRECT ELECTRICAL NOTE |
| | 22. |
| | |
| | 7] ADD GENERAL ELECTRICAL NOTE FOR TAMPER RESISTANT |
| | RECEPTACLES IN ACCORDANCE WITH NEC 406.12. |
| | |
| | 8] ALL MEANS OF EGRESS STAIRWAYS IN COMMON AREAS WILL |
| | REQUIRE EXIT LIGHTS & EMERGENCY LIGHTS THROUGH-OUT THE |
| | EXIT DISCHARGE. EXTERIOR ILLUMINATION IS REQUIRED TO |
| | ILLUMINATE EGRESS PATH UNTIL PUBLIC WAY IS SAFELY |
| | REACHED. FBC 1011 & 1006 (SHOW COMPLIANCE). |
| | |
| | 9] EXIT & EMERGENCY LIGHTS SHALL BE FED AHEAD OF LOCAL |
| | LIGHTING AREA SERVED. NEC 700.12(F)(4) |
| | |
| | 10] FIRE MARSHALL SHALL DETERMINE IF A FIRE ALARM IS |
| | REQUIRED OR IF SINGLE STATION SMOKE ALARMS WILL SUFFICE |
| | ENOUGH FIRE PROTECTION. |
| | |
| | 11] EACH OCCUPANT SHALL HAVE READY ACCESS TO ALL |
| | OVERCURRENT DEVICES, AS CONFIGURED ACCESSIBILITY IS |
| | LIMITED. PLEASE SEE NEC 240.24(B) |
| | |
| | 12] PROVIDE AIC CALCULATIONS TO VERIFY SHORT-CIRCUIT |
| | RATINGS OF ELECTRICAL EQUIPMENT. NEC 110.10 & 110.9 |
| | |
| | 13] CLARIFY RISER DIAGRAM FEEDER LAYOUT, EACH UNIT THAT |
| | WILL BE INDIVIDUALLY METERED SHALL HAVE ITS DEDICATED |
| | PANEL BOARD WITH ALL ASSOCIATED LOADS TERMINATING |
| | ACCORDINGLY. ELIMINATE PANELS "C1", "C2", "C3" TO |
| | COMPLY WITH NEC REQUIREMENTS & SHOW PANEL SCHEDULES |
| | WITH MATCHING FLOOR PLAN CIRCUITS. ADJUST RISER-DIAGRAM |
| | DETAIL TO REFLECT ALL CONDUIT & WIRE SIZES. FBC |
| | 107.3.5.3 |
| | |
| | - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| | QUESTIONS, PLEASE DON?T HESITATE TO CONTACT ME |
| | DIRECTLY. |
| | |
| | 1ST REVIEW FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |