Plan Review Notes
Plan Review Notes For Permit 16100891
Permit Number 16100891
Review Stop B
Sequence Number 1
Notes
Date Text
2016-11-16 12:05:33BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. STATE GOVERNING CODES ON PLANS: 2014 FBC 5TH
 EDITION, 2011 NEC.
 2. DESIGN PROFESSIONALS SIGNATURE AND SEAL APPEAR TO BE
 PHOTO COPIED. DESIGNER OF RECORD TO SIGN AND SEAL PLANS
 PER FAC 61G1-16.001.
 3. VERTICAL RE-INFORCEMENT FOR COLUMNS SHALL COMPLY
 WITH FBC 606.12.3.2 & 606.12.3.3.
  
 FBC-107.1 GENERAL - FAC 61G1-16.004 - A TITLE BLOCK
 MUST APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION IDENTIFICATION SHEETS THAT
 ARE REQUIRED TO BE SIGNED AND SEALED. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION
 NUMBER OF THE PERSON SEALING THE DOCUMENT.
 (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE
 REVISED.
  
 61G1-16.001 ARCHITECT?S AND INTERIOR DESIGNER?S SEAL.
 EACH ARCHITECT AND INTERIOR DESIGNER SHALL ACQUIRE A
 SEAL WITH WHICH SHE OR HE SHALL IDENTIFY ALL PLANS,
 SPECIFICATIONS OR REPORTS PREPARED OR ISSUED BY HER OR
 HIM AND FILED FOR PUBLIC RECORD. THE SEAL SHALL BE
 CAPABLE OF LEAVING A PERMANENT INK REPRESENTATION OR
 OTHER FORM OF EMBOSSING OR OPAQUE AND PERMANENT
 IMPRESSION, WHICH ALSO MAY BE COMPUTER GENERATED
 IMPRESSIONS, ON THE SURFACE OF PRINTS OR OTHER
 DUPLICATIONS OF DRAWINGS, AND, AS APPROPRIATE, UPON
 SPECIFICATION PAGES, AND OTHER ARTICLES OF SERVICE.
 WHERE REQUIRED, ELECTRONIC FILES MAY BE SEALED IN
 ACCORDANCE WITH RULE 61G1-16.005, F.A.C.
  
 R606.12.3.2 MINIMUM REINFORCEMENT REQUIREMENTS FOR
 MASONRY WALLS.
 MASONRY WALLS OTHER THAN THOSE COVERED BY SECTION
 R606.12.2.2.3 SHALL BE REINFORCED IN BOTH THE VERTICAL
 AND HORIZONTAL DIRECTION. THE SUM OF THE
 CROSS-SECTIONAL AREA OF HORIZONTAL AND VERTICAL
 REINFORCEMENT SHALL BE AT LEAST 0.002 TIMES THE GROSS
 CROSSSECTIONAL AREA OF THE WALL, AND THE MINIMUM
 CROSS-SECTIONAL AREA IN EACH DIRECTION SHALL BE NOT
 LESS THAN 0.0007 TIMES THE GROSS CROSS-SECTIONAL AREA
 OF THE WALL. REINFORCEMENT SHALL BE UNIFORMLY
 DISTRIBUTED. TABLE R606.12.3.2 SHOWS THE MINIMUM
 REINFORCING BAR SIZES REQUIRED FOR VARYING THICKNESSES
 OF MASONRY WALLS. THE MAXIMUM SPACING OF REINFORCEMENT
 SHALL BE 48 INCHES (1219 MM) PROVIDED THAT THE WALLS
 ARE SOLID GROUTED AND CONSTRUCTED OF HOLLOW OPEN-END
 UNITS, HOLLOW UNITS LAID WITH FULL HEAD JOINTS OR TWO
 WYTHES OF SOLID UNITS. THE MAXIMUM SPACING OF
 REINFORCEMENT SHALL BE 24 INCHES (610 MM) FOR ALL OTHER
 MASONRY.
  
 R606.12.3.3 MINIMUM REINFORCEMENT FOR MASONRY COLUMNS.
 LATERAL TIES IN MASONRY COLUMNS SHALL BE SPACED NOT
 MORE THAN 8 INCHES (203 MM) ON CENTER AND SHALL BE AT
 LEAST 3/8-INCH (9.5 MM) DIAMETER. LATERAL TIES SHALL BE
 EMBEDDED IN GROUT.
  