Plan Review Notes
Plan Review Notes For Permit 16100880
Permit Number 16100880
Review Stop P
Sequence Number 2
Notes
Date Text
2017-01-24 17:39:552ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 2ND REQUEST
  
 1. BATH # 1 ELEVATIONS BATH#2 MIRRORED PER FBC ACC
 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 2. SANITARY RISER NEW NURSING STATION THE SINK IS NOTE
 VENTED. PER FBC PL 901.2.1
  
 3. SANITARY RISER BATH # 3 NEW SINK NOT VENTED. PER FBC
 PL 901.2.1
  
 4. SANITARY RISER BATH # 3 #4 REMOVE VENTS FROM WC NOT
 NEEDED BATHROOM VENTED BY SINK VENT. PER FBC PL 901.2.1
  
 5. KITCHEN AND NEW PHARMACY SANITARY TABLE SINK LABELED
 AS HAND SINK PLEASE CLARIFY. PER WPB AMEN TO FBC
 107.2.1.
  
 6. SHOW VENT FOR TABLE SINK SLOP SINK AND EXISTING
 WASHING MACHINE. PER FBC PL 901.2.1
  
 7. THE 3 COMPARTMENT SINK , FLOOR DRAIN AND TABLE SINK
 AND SLOPE SINK ARE REQUIRED TO CONNECT TO A GREASE
 INTERCEPTOR. PER FBC PL 1003.1
  
 8. PLEASE PROVIDE MANUFACTURE SPECIFICATION AND
 CALCULATIONS FOR GREASE INTERCEPTOR. PER WPB AMEN TO
 FBC 107.2.1.
  
 9. THE FLOOR DRAIN SHALL BE EQUIPPED WITH A TRAP
 PRIMER. FBC PL 1002.4