| Plan Review Notes For Permit 16100873 |
| Permit Number |
16100873 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-01-25 11:08:57 | 3RD REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | PASSED WITH THE FOLLOWING PROVISO'S | | | | | | 1] EXIT & EMERGENCY LIGHTING REQUIRED PER FBC 1006 & | | | 1011. (MEANS OF EGRESS ILLUMINATION FOR EXIT DISCHARGE) | | | | | | 2] ELECTRICAL LOAD CALCULATIONS, SINGLE LINE RISER | | | DIAGRAM INCLUDING WIRE & CONDUIT SIZES, & PANEL | | | SCHEDULES SHALL BE SUBMITTED FOR TENANT PERMIT # | | | 16100033. | | | | | | 3] FBC-E SECTION C101.4.4 CHANGE IN OCCUPANCY OR USE. | | | SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD | | | RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL | | | OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. | | | WHERE THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE | | | C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1) | | | OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY | | | WITH SECTION C405.5. | | | | | | 4] ELECTRIC WATER FOUNTAINS REQUIRES GFCI PROTECTION | | | PER NEC 422.52 | | 2017-01-25 10:44:27 | ROUTED TO SH. |
|