Plan Review Notes
Plan Review Notes For Permit 16100873
Permit Number 16100873
Review Stop B
Sequence Number 2
Notes
Date Text
2016-12-13 12:07:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 2. THIS PROJECT INCLUDES A CHANGE OF OCCUPANCY. SEE FBC
 5TH EDITION EXISTING BUILDING CHAPTER 10. REVISE PLAN
 TO SHOW COMPLIANCE WITH ALL REQUIREMENTS.
  
 2ND REVIEW, INFORMATION REGARDING THE EXISTING
 OCCUPANCY WAS NOT PROVIDED.
  
 COMPLIANCE WITH THE FOLLOWING IS NOT CLEAR:
  
 FBC EB TABLE 1012.5, FBC B TABLE 503, AS CHANGE OF
 OCCUPANCY IS PROPOSED TO A HIGHER HAZARD, COMPLIANCE
 WITH FBC B CHAPTER 5 IS REQUIRED. IT APPEARS THAT THE
 PROPOSED NEW OCCUPANCY MAY COMPLY, BUT REQUIRES
 CALCULATIONS AND INFORMATION REGARDING THE EXISTING
 OCCUPANCIES TO BE PROVIDED FBC B 503.1.
  
 FBC EB TABLE 1012.6, APPEARS TO COMPLY, BUT NO
 INFORMATION PROVIDED (FROM S1 OR S2 TO A OR B? B TO A?)
  
 6. SEE IMPACT FEE REVIEW.
  
 THIS IS REQUIRED PRIOR TO PERMIT ISSUANCE BUT MAY BE
 DONE AFTER ALL REVIEWS HAVE PASSED.
  
 NEW COMMENT:
  
 THE DOOR IN THE WOMENS RESTROOM SWINGS INTO THE CLEAR
 FLOOR SPACE, FBC A 603.2.3.
  
 PROVISO, DETAILS FOR TOILET DO NOT COMPLY, HEIGHT TO BE
 MEASURED AT TOP OF SEAT, FBC A 604.4, REVISE DETAILS.
  
 * * * * * * * * * * * * *
  
 THE FOLLOWING ITEMS WERE ADDRESSED IN A RESPONSE
 LETTER. IF THE SHEETS ARE REVISED DUE TO OTHER TRADES,
 REVISE THE PLAN TO INCORPORATE THE INFORMATION.
  
 1. PROVISO; SHOP DRAWINGS OR PRODUCT APPROVAL REQUIRED
 FOR REAR EXIT DOOR, FBC 1008.
  
 3. PROVIDE A DETAIL FOR THE STORAGE RACKS, FBC 107.
 PROVIDE INFORMATION REGARDING THE EQUIPMENT TO BE
 STORED THERE AND THE WEIGHT OF ITEMS TO BE STORED ON
 THE RACKS.
  
 8. ALL DOORS AND GATES ARE TO INCLUDE PANIC HARDWARE,
 FBC 1008.1.10, 1008.2. REVISE PLAN TO SPECIFY. (DOORS
 SPECIFIED, REVISE TO INCLUDE GATES)
  
 10. INCORPORATE INFORMATION REGARDING THE BENCH SEATS
 INTO THE PLAN, FBC 5TH EDITION ACCESSIBILITY 903. PER
 RESPONSE LETTER THEY ARE MOVEABLE AND BACKLESS.
  
 18. THE SLOPE EXCEEDS THE MAXIMUM SLOPE OF 1:20 (1:12
 SHOWN), FBC A 403.3. THIS APPEARS TO BE A RAMP; RISE
 CANNOT EXCEED 6 INCHES. IF RISE EXCEEDS 6 INCHES,
 HANDRAILS AND EDGE PROTECTION ARE REQUIRED (AND A
 REVISION IS REQUIRED).
  
 19. REVISE PLAN TO INCLUDE THE EXIT DISCHARGE TO THE
 PUBLIC WAY, FBC 1027. SHOW COMPLIANCE WITH ALL
 REQUIREMENTS, INCLUDING ILLUMINATION.
  
  