| 2016-12-13 12:07:04 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 2. THIS PROJECT INCLUDES A CHANGE OF OCCUPANCY. SEE FBC |
| | 5TH EDITION EXISTING BUILDING CHAPTER 10. REVISE PLAN |
| | TO SHOW COMPLIANCE WITH ALL REQUIREMENTS. |
| | |
| | 2ND REVIEW, INFORMATION REGARDING THE EXISTING |
| | OCCUPANCY WAS NOT PROVIDED. |
| | |
| | COMPLIANCE WITH THE FOLLOWING IS NOT CLEAR: |
| | |
| | FBC EB TABLE 1012.5, FBC B TABLE 503, AS CHANGE OF |
| | OCCUPANCY IS PROPOSED TO A HIGHER HAZARD, COMPLIANCE |
| | WITH FBC B CHAPTER 5 IS REQUIRED. IT APPEARS THAT THE |
| | PROPOSED NEW OCCUPANCY MAY COMPLY, BUT REQUIRES |
| | CALCULATIONS AND INFORMATION REGARDING THE EXISTING |
| | OCCUPANCIES TO BE PROVIDED FBC B 503.1. |
| | |
| | FBC EB TABLE 1012.6, APPEARS TO COMPLY, BUT NO |
| | INFORMATION PROVIDED (FROM S1 OR S2 TO A OR B? B TO A?) |
| | |
| | 6. SEE IMPACT FEE REVIEW. |
| | |
| | THIS IS REQUIRED PRIOR TO PERMIT ISSUANCE BUT MAY BE |
| | DONE AFTER ALL REVIEWS HAVE PASSED. |
| | |
| | NEW COMMENT: |
| | |
| | THE DOOR IN THE WOMENS RESTROOM SWINGS INTO THE CLEAR |
| | FLOOR SPACE, FBC A 603.2.3. |
| | |
| | PROVISO, DETAILS FOR TOILET DO NOT COMPLY, HEIGHT TO BE |
| | MEASURED AT TOP OF SEAT, FBC A 604.4, REVISE DETAILS. |
| | |
| | * * * * * * * * * * * * * |
| | |
| | THE FOLLOWING ITEMS WERE ADDRESSED IN A RESPONSE |
| | LETTER. IF THE SHEETS ARE REVISED DUE TO OTHER TRADES, |
| | REVISE THE PLAN TO INCORPORATE THE INFORMATION. |
| | |
| | 1. PROVISO; SHOP DRAWINGS OR PRODUCT APPROVAL REQUIRED |
| | FOR REAR EXIT DOOR, FBC 1008. |
| | |
| | 3. PROVIDE A DETAIL FOR THE STORAGE RACKS, FBC 107. |
| | PROVIDE INFORMATION REGARDING THE EQUIPMENT TO BE |
| | STORED THERE AND THE WEIGHT OF ITEMS TO BE STORED ON |
| | THE RACKS. |
| | |
| | 8. ALL DOORS AND GATES ARE TO INCLUDE PANIC HARDWARE, |
| | FBC 1008.1.10, 1008.2. REVISE PLAN TO SPECIFY. (DOORS |
| | SPECIFIED, REVISE TO INCLUDE GATES) |
| | |
| | 10. INCORPORATE INFORMATION REGARDING THE BENCH SEATS |
| | INTO THE PLAN, FBC 5TH EDITION ACCESSIBILITY 903. PER |
| | RESPONSE LETTER THEY ARE MOVEABLE AND BACKLESS. |
| | |
| | 18. THE SLOPE EXCEEDS THE MAXIMUM SLOPE OF 1:20 (1:12 |
| | SHOWN), FBC A 403.3. THIS APPEARS TO BE A RAMP; RISE |
| | CANNOT EXCEED 6 INCHES. IF RISE EXCEEDS 6 INCHES, |
| | HANDRAILS AND EDGE PROTECTION ARE REQUIRED (AND A |
| | REVISION IS REQUIRED). |
| | |
| | 19. REVISE PLAN TO INCLUDE THE EXIT DISCHARGE TO THE |
| | PUBLIC WAY, FBC 1027. SHOW COMPLIANCE WITH ALL |
| | REQUIREMENTS, INCLUDING ILLUMINATION. |
| | |
| | |