| 2016-11-08 16:15:48 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. VALUATIONS SEEMS LOW PLEASE PROVIDE BONA FIDE SIGNED |
| | CONTRACTS WITH PRICE BREAK DOWN FOR ALL TRADES. PER WPB |
| | AMEND. TO FBC 109.3 |
| | |
| | 2. ALL ACCESSIBILITY ELEMENTS SHALL COMPLY WITH THE |
| | FLORIDA BUILDING CODE |
| | 5TH EDITION (2014) ACCESSIBILITY WITCH DIFFERS FROM THE |
| | ADA/ ANZI -A117.1 |
| | PLEASE CHECK YOUR NOTES TO ENSURE THEY ALL COMPLY WITH |
| | FBC ACC AND REMOVE REFERENCE TO ADA/ ANZI-A117.1 |
| | PER WPB AMENS. TO FBC 107.2.1 |
| | |
| | 3. SHOW COMPLIANCE FORTOILET PAPER DISPENSERS SHALL |
| | COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM) |
| | MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE |
| | WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. PER FBC ACC 604.7 |
| | |
| | 4. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP |
| | OF THE GRIPPING SURFACE NOT CENTERLINE OF BAR. PER FBC |
| | ACC 609.4 |
| | |
| | 5. THE REAR WALLL GRAB BAR SHALL BE 36 INCHES (915 MM) |
| | LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE |
| | WATER CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND |
| | 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE IF TOILET |
| | IS SET AT 18" OFF SIDE WALL YOU WILL HAVE 6" FROM END |
| | OF THE BAR TO THE SIDE WAL YOU ARE SHOWING 2" PLEASE |
| | CLARIFY . PER FBC ACC 604.5.2 |
| | |
| | 6. A WATER FOUNTAIN COMPLYING WITH FBC ACC 602 AND FBC |
| | PL [B] 410.2 IS REQUIRED. |
| | |
| | 7. PLEASE PROVIDE SANITARY AND WATER RISER DIAGRAM. PER |
| | WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 8. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | 9. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1 |
| | |
| | |