| 2016-11-02 18:23:40 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | - NO ELECTRICAL INFORMATION, PLEASE PROVIDE AN | | | ELECTRICAL SCOPE OF WORK. INCLUDE THE FOLLOWING ITEMS | | | | | | 1] SHOW A DETAIL FOR OBSTRUCTED AND UNBOSTRUCTED REACH | | | RANGES OF DEVICES IN ACCORDANCE WITH FBC-A SECTION 308. | | | | | | 2] SHOW A DETAIL FOR THE MEANS OF SUPPORT OF THE LAY IN | | | LUMINAIRE TO THE SUSPENDED CEILING PER NEC 410.36(B). | | | | | | 3] THE ADA RAMP WILL BE A MEANS OF EGRESS EXIT | | | DISCHARGE THEREFORE ILLUMINATION IS REQUIRED. | | | FBC-1006.1 (SHOW COMPLIANCE). |
|