| 2016-11-07 15:06:42 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. PLAN SHOWS AN EXISTING DOOR TO HAVE A PANIC BAR |
| | INSTALLED. PROVIDE PRODUCT INFORMATION FOR THE EXISTING |
| | DOOR AND FOR THE PROPOSED PANIC HARDWARE. EXTERIOR |
| | DOORS ARE TESTED WITH HARDWARE, SO IT IS NOT CLEAR HOW |
| | THIS WILL AFFECT THE INTEGRITY OF THE DOOR, FBC 1609, |
| | 107. |
| | |
| | 2. THIS PROJECT INCLUDES A CHANGE OF OCCUPANCY. SEE FBC |
| | 5TH EDITION EXISTING BUILDING CHAPTER 10. REVISE PLAN |
| | TO SHOW COMPLIANCE WITH ALL REQUIREMENTS. |
| | |
| | 3. PROVIDE A DETAIL FOR THE STORAGE RACKS, FBC 107. |
| | PROVIDE INFORMATION REGARDING THE EQUIPMENT TO BE |
| | STORED THERE AND THE WEIGHT OF ITEMS TO BE STORED ON |
| | THE RACKS. |
| | |
| | 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, |
| | INCLUDING A COST BREAKDOWN FOR ALL WORK INCLUDING LABOR |
| | AND MATERIALS, OVERHEAD AND PROFIT, INCLUDING ITEMS |
| | ALREADY INSTALLED WITHOUT PERMIT (PROVIDE VALUE OF WHAT |
| | A CONTRACTOR WOULD HAVE CHARGED FOR THE WORK TO BE |
| | DONE), FBC 109. VALUE IS TOO LOW. FAILURE TO PROVIDE AN |
| | ACCURATE VALUE WILL RESULT IN PERMIT ISSUANCE DELAY. |
| | |
| | 5. THE RATIONALE FOR BUSINESS OCCUPANCY IS NOT CLEAR. |
| | REVISE PLAN TO INCLUDE INFORMATION AS TO USE OF EACH |
| | AREA. THE TWO SMALL OFFICES ARE BUSINESS, BUT THE REST |
| | OF THE SPACE APPEARS TO BE ASSEMBLY, FBC CHAPTER 3. |
| | |
| | 6. SEE IMPACT FEE REVIEW. |
| | |
| | 7. REVISE PLAN TO INCLUDE INFORMATION REGARDING THE |
| | GAME AREA. PROVIDE A SPECIFICATION FOR THE NETTING AND |
| | THE DOORS, FBC 107. |
| | |
| | 8. ALL DOORS AND GATES ARE TO INCLUDE PANIC HARDWARE, |
| | FBC 1008.1.10, 1008.2. REVISE PLAN TO SPECIFY. |
| | |
| | 9. SEE FBC 303.3, EXPLAIN RATIONALE FOR OCUPANCY A2, |
| | USES INTENDED FOR FOOD AND DRINK. |
| | |
| | 10. PROVIDE A DETAIL FOR THE BENCH SEATS, FBC 5TH |
| | EDITION ACCESSIBILITY 903. |
| | |
| | 11. PROVIDE A DETAIL FOR THE SALES AND SERVICE COUNTER |
| | OR CHECK OUT AISLE, FBC 5TH EDITION ACCESSIBILITY 9 04. |
| | |
| | 12. IDENTIFY THE UNIDENTIFIED RECTANGLE ADJACENT TO THE |
| | DOOR IN THE EQUIPMENT AREA, FBC 107. |
| | |
| | 13. REVISE PLAN TO SHOW THE 18 INCH MANEUVERING |
| | CLEARANCE FOR THE DOOR FOR THE UNIDENTIFIED ROOM |
| | ADJACENT TO THE PROPOSED REST ROOMS A2, FBC 5TH EDITION |
| | ACCESSIBILITY 404.2.4.1. |
| | |
| | 14. PROPOSED FLOOR PLAN INCLUDES DEMO AREA FOR THE REST |
| | ROOMS BUT NOT THE PROPSED PLAN, REVISE PLAN TO BE |
| | CONSISTENT WITH THE NAME OF THE DETAIL. IF NECESSARY, |
| | PROVIDE A DEMO PLAN TO CLARIFY, FBC 107. |
| | |
| | 15. A3 RAMP DETAIL HAS OLD CODE REFERENCE, REVISE TO |
| | CURRENT, FBC 5TH EDITION ACCESSIBILITY. |
| | |
| | 16. REVISE PLAN TO SHOW THE RISE OF THE RAMP, FBC 5TH |
| | EDITION ACCESSIBILITY 405.6. |
| | |
| | 17. REAR DOOR AT RAMP, CLARIFY DOOR SWING. ONE PAGE |
| | SHOWS A RIGHT HAND, ANOTHER PAGE SHOWS LEFT. DOORS ARE |
| | TO HAVE 18 IN MANEUVERING CLEARANCE ON THE PULL SIDE, |
| | FBC 5TH EDITION ACCESSIBILITY 404.2.4.1. |
| | |
| | 18. RAMP DETAIL SHOWS A SLOPE DOWN, A LANDING, AND A |
| | RAMP UP. REVISE PLAN TO INCLUDE THE SLOPE, FBC 107. |
| | |
| | 19. REVISE PLAN TO INCLUDE THE EXIT DISCHARGE TO THE |
| | PUBLIC WAY, FBC 1027. SHOW COMPLIANCE WITH ALL |
| | REQUIREMENTS, INCLUDING ILLUMINATION. |
| | |
| | 20. HANDRAIL EXTENSION REQUIRED AT THE TOP OF THE RAMP, |
| | FBC 5TH EDITION 505.10. |
| | |
| | 21. SHOW THE ACCESSIBLE ROUTE FROM THE PUBLIC WAY AND |
| | FROM ACCESSIBLE PARKING SPACE TO THE ALTERED AREA, FBC |
| | 5TH EDITION 202.4. |
| | |