Plan Review Notes
Plan Review Notes For Permit 16100873
Permit Number 16100873
Review Stop B
Sequence Number 1
Notes
Date Text
2016-11-07 15:06:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLAN SHOWS AN EXISTING DOOR TO HAVE A PANIC BAR
 INSTALLED. PROVIDE PRODUCT INFORMATION FOR THE EXISTING
 DOOR AND FOR THE PROPOSED PANIC HARDWARE. EXTERIOR
 DOORS ARE TESTED WITH HARDWARE, SO IT IS NOT CLEAR HOW
 THIS WILL AFFECT THE INTEGRITY OF THE DOOR, FBC 1609,
 107.
  
 2. THIS PROJECT INCLUDES A CHANGE OF OCCUPANCY. SEE FBC
 5TH EDITION EXISTING BUILDING CHAPTER 10. REVISE PLAN
 TO SHOW COMPLIANCE WITH ALL REQUIREMENTS.
  
 3. PROVIDE A DETAIL FOR THE STORAGE RACKS, FBC 107.
 PROVIDE INFORMATION REGARDING THE EQUIPMENT TO BE
 STORED THERE AND THE WEIGHT OF ITEMS TO BE STORED ON
 THE RACKS.
  
 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB,
 INCLUDING A COST BREAKDOWN FOR ALL WORK INCLUDING LABOR
 AND MATERIALS, OVERHEAD AND PROFIT, INCLUDING ITEMS
 ALREADY INSTALLED WITHOUT PERMIT (PROVIDE VALUE OF WHAT
 A CONTRACTOR WOULD HAVE CHARGED FOR THE WORK TO BE
 DONE), FBC 109. VALUE IS TOO LOW. FAILURE TO PROVIDE AN
 ACCURATE VALUE WILL RESULT IN PERMIT ISSUANCE DELAY.
  
 5. THE RATIONALE FOR BUSINESS OCCUPANCY IS NOT CLEAR.
 REVISE PLAN TO INCLUDE INFORMATION AS TO USE OF EACH
 AREA. THE TWO SMALL OFFICES ARE BUSINESS, BUT THE REST
 OF THE SPACE APPEARS TO BE ASSEMBLY, FBC CHAPTER 3.
  
 6. SEE IMPACT FEE REVIEW.
  
 7. REVISE PLAN TO INCLUDE INFORMATION REGARDING THE
 GAME AREA. PROVIDE A SPECIFICATION FOR THE NETTING AND
 THE DOORS, FBC 107.
  
 8. ALL DOORS AND GATES ARE TO INCLUDE PANIC HARDWARE,
 FBC 1008.1.10, 1008.2. REVISE PLAN TO SPECIFY.
  
 9. SEE FBC 303.3, EXPLAIN RATIONALE FOR OCUPANCY A2,
 USES INTENDED FOR FOOD AND DRINK.
  
 10. PROVIDE A DETAIL FOR THE BENCH SEATS, FBC 5TH
 EDITION ACCESSIBILITY 903.
  
 11. PROVIDE A DETAIL FOR THE SALES AND SERVICE COUNTER
 OR CHECK OUT AISLE, FBC 5TH EDITION ACCESSIBILITY 9 04.
  
 12. IDENTIFY THE UNIDENTIFIED RECTANGLE ADJACENT TO THE
 DOOR IN THE EQUIPMENT AREA, FBC 107.
  
 13. REVISE PLAN TO SHOW THE 18 INCH MANEUVERING
 CLEARANCE FOR THE DOOR FOR THE UNIDENTIFIED ROOM
 ADJACENT TO THE PROPOSED REST ROOMS A2, FBC 5TH EDITION
 ACCESSIBILITY 404.2.4.1.
  
 14. PROPOSED FLOOR PLAN INCLUDES DEMO AREA FOR THE REST
 ROOMS BUT NOT THE PROPSED PLAN, REVISE PLAN TO BE
 CONSISTENT WITH THE NAME OF THE DETAIL. IF NECESSARY,
 PROVIDE A DEMO PLAN TO CLARIFY, FBC 107.
  
 15. A3 RAMP DETAIL HAS OLD CODE REFERENCE, REVISE TO
 CURRENT, FBC 5TH EDITION ACCESSIBILITY.
  
 16. REVISE PLAN TO SHOW THE RISE OF THE RAMP, FBC 5TH
 EDITION ACCESSIBILITY 405.6.
  
 17. REAR DOOR AT RAMP, CLARIFY DOOR SWING. ONE PAGE
 SHOWS A RIGHT HAND, ANOTHER PAGE SHOWS LEFT. DOORS ARE
 TO HAVE 18 IN MANEUVERING CLEARANCE ON THE PULL SIDE,
 FBC 5TH EDITION ACCESSIBILITY 404.2.4.1.
  
 18. RAMP DETAIL SHOWS A SLOPE DOWN, A LANDING, AND A
 RAMP UP. REVISE PLAN TO INCLUDE THE SLOPE, FBC 107.
  
 19. REVISE PLAN TO INCLUDE THE EXIT DISCHARGE TO THE
 PUBLIC WAY, FBC 1027. SHOW COMPLIANCE WITH ALL
 REQUIREMENTS, INCLUDING ILLUMINATION.
  
 20. HANDRAIL EXTENSION REQUIRED AT THE TOP OF THE RAMP,
 FBC 5TH EDITION 505.10.
  
 21. SHOW THE ACCESSIBLE ROUTE FROM THE PUBLIC WAY AND
 FROM ACCESSIBLE PARKING SPACE TO THE ALTERED AREA, FBC
 5TH EDITION 202.4.
  