| 2016-12-08 13:54:20 | RESIDENTIAL (R3) ALTERATIONS SECOND MECHANICAL REVIEW |
| | CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | NOTE: |
| | ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN |
| | REVIEW FEE IF PLANS ARE DENIED THREE OR MORE TIMES AS |
| | REQUIRED BY FLORIDA STATUTE 553.80(2)(B). |
| | |
| | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. |
| | INFORMATION SUBMITTED IS ONLY THE SUMMARY. NEED TO |
| | PROVIDE THE COMPLETE CALCULATIONS SHOWING THE ACTUAL |
| | BUILDING ORIENTATION AND COMPLETE EQUIPMENT INFORMATION |
| | AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. COMPLETE CALCULATIONS WERE |
| | NOT SUBMITTED. AND, HANDWRITTEN INFORMATION IS NOT |
| | ALLOWED. |
| | |
| | 2- A/C PLAN SUBMITTED: |
| | A) A/C PLAN IS NOT LEGIBLE. THERE IS TOO MUCH |
| | OVERLAPPING BACKGROUND INFORMATION. PROVIDE LEGIBLE |
| | PLAN. SEC. 107.2.1.4 CITY AMENDMENTS. |
| | RESPONSE: REPEAT COMMENT. PLAN NOT REVISED. TOO MUCH |
| | BACKGROUND INFORMATION. PLAN NOT LEGIBLE. |
| | |
| | B) EQUIPMENT SHOWN ON PLANS DON'T MATCH EQUIPMENT |
| | LISTED ON THE NEW SUMMARY SUBMITTED. REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | RESPONSE: REPEAT COMMENT. COMPLETE CALCULATIONS WERE |
| | NOT SUBMITTED. AND, HANDWRITTEN INFORMATION IS NOT |
| | ALLOWED. |
| | |
| | C) A/C PLAN DON'T SHOW COMPLIANCE WITH THE BALANCED |
| | RETURN AIR AS REQUIRED BY SEC. M1602.4 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). TYPICALLY, |
| | TRANSFER DUCTS OR TRANSFER GRILLES ARE INSTALLED FOR |
| | BALANCED RETURN AIR. AND, THE DOOR HAS AT LEAST AN |
| | UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER RETURN |
| | AIR BALANCE. SEE EXCEPTIONS ON SEC. M1602.4 |
| | FBC-RESIDENTIAL. NOTE: THERE IS A NOTE STATING "RETURN |
| | AIR BALANCE WILL BE PROVIDED BY UNDERCUTTING ALL DOORS |
| | A MIN. OF 1-1/2" OFF THE FINISHED FLOOR". THIS MAY NOT |
| | BE ENOUGH TO ACCOMPLISH TO BALANCED RETURN AIR. A |
| | BALANCED RETURN TEST NEED TO BE PERFORMED TO VERIFY |
| | COMPLIANCE. ENGINEER OF RECORD TO SPECIFY ON PLANS THAT |
| | BALANCE TEST IS REQUIRED OR SHOW COMPLIANCE WITH THE |
| | EXCEPTIONS OF SEC. M1602.4. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |