2016-12-07 18:38:53REAR GUEST HOUSE:
 RESIDENTIAL (R3) ALTERATIONS THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
  
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN
 REVIEW FEE IF PLANS ARE DENIED THREE OR MORE TIMES AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B).
  
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. OWNER'S NAME WAS NOT
 PROVIDED. ALSO, REVISE THE PERMIT OFFICE INFORMATION.
 "BUILDING DEPARTMENT" IS NOT THE PERMIT OFFICE. THE
 PERMIT OFFICE IS WEST PALM BEACH.
  
 B) ITEM #1 IS INCORRECT. THIS IS NOT NEW CONSTRUCTION.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. ORIGINAL CALCULATIONS WERE
 NOT REVISED. NOTE: HANDWRITTEN INFORMATION IS NOT
 ALLOWED. ALL THE INFORMATION NEEDS TO BE CHANGED ON THE
 ORIGINAL PROGRAM.
  
 C) NUMBER OF BEDROOMS ON ITEM #4 IS INCORRECT. SEE
 PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. ORIGINAL CALCULATIONS WERE
 NOT REVISED. NOTE: HANDWRITTEN INFORMATION IS NOT
 ALLOWED. ALL THE INFORMATION NEEDS TO BE CHANGED ON THE
 ORIGINAL PROGRAM.
  
 D) ITEM #5 STATES THAT CALCULATIONS WERE DONE FOR A
 WORST CASE SCENARIO. CALCULATIONS NEED TO BE DONE FOR
 THE ACTUAL ORIENTATION OF THE BUILDING. REVISE AS
 REQUIRED TO MATCH PLANS AND SURVEY. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. ORIGINAL CALCULATIONS WERE
 NOT REVISED. NOTE: HANDWRITTEN INFORMATION IS NOT
 ALLOWED. ALL THE INFORMATION NEEDS TO BE CHANGED ON THE
 ORIGINAL PROGRAM.
  
 E) PROVIDE MANUFACTURER'S INFORMATION FOR THE WINDOWS
 AND DOORS SHOWING COMPLIANCE WITH THE U-FACTOR AND SHGC
 FACTOR SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7.
 NOTE: THIS IS ONLY REQUIRED WHEN THE PERSON PREPARING
 THE CALCULATIONS IS TAKING A FACTOR OTHER THAN THE
 DEFAULT FACTOR OF THE ENERGY CALCULATIONS SOFTWARE.
 SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE: REPEAT COMMENT. ORIGINAL CALCULATIONS WERE
 NOT REVISED. NOTE: HANDWRITTEN INFORMATION IS NOT
 ALLOWED. ALL THE INFORMATION NEEDS TO BE CHANGED ON THE
 ORIGINAL PROGRAM.
  
 F) REVISE ITEM #10. R-30 INSULATION INSTALLED ON 2 X 10
 ROOF JOIST DOESN'T COMPLY WITH THE VENTILATION
 REQUIREMENTS OF SEC. R806.3 FBC-RESIDENTIAL. NEED A
 MINIMUM OF 1 INCH SPACE BETWEEN THE INSULATION AND THE
 ROOF SHEATHING. REVISE AS REQUIRED.
  
 G) ACCORDING TO PLANS AND ZONING REQUIREMENTS, THERE IS
 NOT KITCHEN IN THIS GUEST HOUSE. REVISE "SPACES"
 INFORMATION ON PAGE 2 OF 4. REVISE KITCHEN INFORMATION
 AND NUMBER OF OCCUPANTS SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. ORIGINAL CALCULATIONS WERE
 NOT REVISED. NOTE: HANDWRITTEN INFORMATION IS NOT
 ALLOWED. ALL THE INFORMATION NEEDS TO BE CHANGED ON THE
 ORIGINAL PROGRAM.
  
 H) REVISE TYPE OF ROOF SPECIFIED ON PAGE 2 OF 4.
 ACCORDING TO PLANS SUBMITTED THIS IS NOT A HIP ROOF.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. ORIGINAL CALCULATIONS WERE
 NOT REVISED. NOTE: HANDWRITTEN INFORMATION IS NOT
 ALLOWED. ALL THE INFORMATION NEEDS TO BE CHANGED ON THE
 ORIGINAL PROGRAM.
  
 I) REVISE INSULATION TYPE SHOWN ON THE CEILING
 INFORMATION ON PAGE 2 OF 4. ACCORDING TO PLANS
 SUBMITTED THERE IS NOT BLOWN INSULATION. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. ORIGINAL CALCULATIONS WERE
 NOT REVISED. NOTE: HANDWRITTEN INFORMATION IS NOT
 ALLOWED. ALL THE INFORMATION NEEDS TO BE CHANGED ON THE
 ORIGINAL PROGRAM.
  
 J) REVISE THE BUILDING ORIENTATION OF THE WALLS, DOORS
 AND WINDOWS ON PAGE 3 OF 4. SEE SURVEY AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. ORIGINAL CALCULATIONS WERE
 NOT REVISED. NOTE: HANDWRITTEN INFORMATION IS NOT
 ALLOWED. ALL THE INFORMATION NEEDS TO BE CHANGED ON THE
 ORIGINAL PROGRAM.
  
 K) REVISE THE WINDOWS OVERHANG SEPARATION SHOWN ON PAGE
 3 OF 4 TO MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. ORIGINAL CALCULATIONS WERE
 NOT REVISED.
  
 2- R-30 BATT INSULATION DOESN'T FIT ON THE SIZE OF ROOF
 JOIST SPECIFIED ON THE NORTH WALL SECTION. REVISE AS
 REQUIRED. COORDINATE WITH THE ENERGY CALCULATIONS.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT. NOTE: THIS APPLIES TO NORTH
 WALL SECTION ON SHEET "2". R-30 BATT INSULATION IN 2 X
 10 ROOF JOIST DON'T COMPLY WITH THE VENTILATION
 REQUIREMENTS. SEC. R806.3 FBC-RESIDENTIAL. REVISE AS
 REQUIRED.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]