Plan Review Notes
Plan Review Notes For Permit 16100865
Permit Number 16100865
Review Stop P
Sequence Number 1
Notes
Date Text
2016-11-18 15:44:322ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE WATER HEATER SHALL NOT BE INSTALLED IN CORNER OF
 THE KITCHEN CABINETS PROPER ACCESS CAN NOT BE PROVIDED.
 PER FBC PL
 P2801.3 LOCATION.
 WATER HEATERS AND STORAGE TANKS SHALL BE INSTALLED IN
 ACCORDANCE WITH SECTION M1305 AND SHALL BE LOCATED AND
 CONNECTED TO PROVIDE ACCESS FOR OBSERVATION,
 MAINTENANCE, SERVICING AND REPLACEMENT.
 M1305.1 APPLIANCE ACCESS FOR INSPECTION SERVICE, REPAIR
 AND REPLACEMENT.
 APPLIANCES SHALL BE ACCESSIBLE FOR INSPECTION, SERVICE,
 REPAIR AND REPLACEMENT WITHOUT REMOVING PERMANENT
 CONSTRUCTION, OTHER APPLIANCES, OR ANY OTHER PIPING OR
 DUCTS NOT CONNECTED TO THE APPLIANCE BEING INSPECTED,
 SERVICED, REPAIRED OR REPLACED. A LEVEL WORKING SPACE
 AT LEAST 30 INCHES DEEP AND 30 INCHES WIDE (762 MM BY
 762 MM) SHALL BE PROVIDED IN FRONT OF THE CONTROL SIDE
 TO SERVICE AN APPLIANCE. INSTALLATION OF ROOM HEATERS
 SHALL BE PERMITTED WITH AT LEAST AN 18-INCH (457 MM)
 WORKING SPACE. A PLATFORM SHALL NOT BE REQUIRED FOR
 ROOM HEATERS.