2016-10-31 14:44:502ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RESIDENTIAL BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE NOTE THAT PREVIOUS COMMENTS HAVE BEEN
 ADDRESSED. NEW PLANS SHOW TWO NEW METERS FOR PROPOSED
 WORK. ZONING WILL HAVE TO APPROVE THE SEPERATE METERING
 TO STUCTURES. ALSO THE SERVICE CONDUCTOR SIZE MUST BE
 SHOWN, AND REVISED GROUNDING ELECTRODE SIZE BASED ON
 SERVICE CONDUCTORS SIZE FOR SERVICE. FBC 107.3.5
 2.FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL FREE
 TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD YOU
 HAVE ANY QUESTIONS OR CONCERNS.
  
  
  