Plan Review Notes
Plan Review Notes For Permit 16100865
Permit Number 16100865
Review Stop B
Sequence Number 1
Notes
Date Text
2016-11-18 09:50:42REAR STRUCTURE: GUEST HOUSE:
 RESIDENTIAL (R3) ALTERATIONS SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) ITEM #1 IS INCORRECT. THIS IS NOT NEW CONSTRUCTION.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 C) NUMBER OF BEDROOMS ON ITEM #4 IS INCORRECT. SEE
 PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) ITEM #5 STATES THAT CALCULATIONS WERE DONE FOR A
 WORST CASE SCENARIO. CALCULATIONS NEED TO BE DONE FOR
 THE ACTUAL ORIENTATION OF THE BUILDING. REVISE AS
 REQUIRED TO MATCH PLANS AND SURVEY. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 E) PROVIDE MANUFACTURER'S INFORMATION FOR THE WINDOWS
 AND DOORS SHOWING COMPLIANCE WITH THE U-FACTOR AND SHGC
 FACTOR SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7.
 NOTE: THIS IS REQUIRED WHEN THE PERSON PREPARING THE
 CALCULATIONS IS TAKING A FACTOR OTHER THAN THE DEFAULT
 FACTOR OF THE ENERGY CALCULATIONS SOFTWARE.
 SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 F) WALL TYPE ON ITEM # 9 NEEDS TO BE COORDINATED WITH
 PLANS. REVISED PLANS SHOW TWO DIFFERENT WALL SECTIONS
 WITH TWO DIFFERENT R-VALUE. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 G) REVISE ITEM #10. R-30 INSULATION DOESN'T FIT ON 2X8
 ROOF JOIST. COORDINATE WITH ITEM #3 BELOW AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 H) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 I) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 J) ACCORDING TO PLANS AND ZONING REQUIREMENTS, THERE IS
 NOT KITCHEN IN THIS GUEST HOUSE. REVISE "SPACES"
 INFORMATION ON PAGE 2 OF 4. REVISE KITCHEN INFORMATION
 AND NUMBER OF OCCUPANTS SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 K) REVISE TYPE OF ROOF SPECIFIED ON PAGE 2 OF 4.
 ACCORDING TO PLANS SUBMITTED THIS IS NOT A HIP ROOF.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 L) REVISE INSULATION TYPE SHOWN ON THE CEILING
 INFORMATION ON PAGE 2 OF 4. ACCORDING TO PLANS
 SUBMITTED THERE IS NOT BLOWN INSULATION. REVISE AS
 REQUIRED. COORDINATE WITH ITEM #1(D) ABOVE. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 M) REVISE THE BUILDING ORIENTATION OF THE WALLS, DOORS
 AND WINDOWS ON PAGE 3 OF 4. SEE SURVEY AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 N) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION
 SHOWN ON PAGE 3 OF 4 TO MATCH PLANS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 O) COMPLETE THE INSPECTION CHECKLIST (TABLE 402.4.1.1
 SUBMITTED) AS REQUIRED BY SEC. R405.4.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
  
 2- PLANS SUBMITTED ARE NOT LEGIBLE. THERE IS TOO MUCH
 OVERLAPPING BACKGROUND INFORMATION THAT DOESN'T ALLOW
 PLANS AND LETTERING TO BE READ. REVISE AS REQUIRED.
 SEC. 107.2.1.4 CITY AMENDMENTS.
  
 3- R-30 BATT INSULATION DOESN'T FIT ON THE SIZE OF ROOF
 JOIST SPECIFIED ON THE NORTH WALL SECTION. REVISE AS
 REQUIRED. COORDINATE WITH THE ENERGY CALCULATIONS.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- THE CARDINAL ORIENTATION SPECIFIED ON THE ALTERATION
 NOTES ON SHEET '1" IS INCORRECT. SEE SURVEY SUBMITTED
 AND REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- TYPICAL WALL SECTION:
 ORIGINAL COMMENT:
 (A) SPECIFY VENTILATION. SEC. R806 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 RESPONSE:
 THE 4"X22" VENTS AT 6' O.C. DON'T PROVIDE CROSS
 VENTILATION WHERE THE ROOF IS FRAMED WITH 2X8 ROOF
 RAFTERS. ONLY A CONTINUOUS VENT WILL PROVIDE CROSS
 VENTILATION. IN ADDITION A MINIMUM OF 1 INCH SPACE IS
 REQUIRED BETWEEN THE INSULATION AND THE ROOF SHEATHING.
 THE THICKNESS OF THE R-30 INSULATION DOESN'T ALLOW THE
 1 INCH SPACE. REVISE AS REQUIRED. ALSO, COORDINATE
 ATTIC INSULATION R-VALUE WITH ITEM #3 ABOVE.
  
 ORIGINAL COMMENT:
 (B) CLEARLY SHOW THE 6" CLEARANCE REQUIRED BY SEC.
 R318.7 FOR TERMITE INSPECTION. WALL SECTION SHOWS THAT
 THE STUCCO IS 2" INTO THE 6" CLEARANCE. REVISE AS
 REQUIRED.
  
 RESPONSE:
 SOUTH WALL SECTION AND NORTH WALL SECTION SUBMITTED
 SHOW STUCCO ALL THE WAY DOWN INTO THE FINISHED GRADE.
 THIS IS NOT ALLOWED. NEED TO PROVIDE THE 6" CLEARANCE.
 REVISE AS REQUIRED.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 ORIGINAL COMMENT:
 A) ALL EXTERIORS DOORS SHOWN ON PLANS.
  
 RESPONSE:
 FLORIDA PRODUCT APPROVAL FL9196.1 SUBMITTED IS FOR
 INSWING DOORS. PLANS SHOW OUTSWING DOORS. NEED TO
 PROVIDE PRODUCT APPROVAL FOR OUTSWING DOORS.
  
 B) HURRICANE SHUTTERS IF DOOR DOESN'T HAVE IMPACT
 GLAZING. AND PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 ORIGINAL COMMENT:
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL NUMBER
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR ENGINEER TO
 LIST THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH
 SPECIFIED CONNECTOR.
  
 RESPONSE:
 COMMENT NOT ADDRESSED. FLORIDA PRODUCT APPROVAL NOT
 SUBMITTED OR FLORIDA PRODUCT APPROVAL NOT LISTED NEXT
 TO EACH SPECIFIED CONNECTOR.
  
 ORIGINAL COMMENT:
 D) WINDOW MULLIONS AS SPECIFIED ON PLANS. AND CLEARLY
 IDENTIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC R301.
  
 RESPONSE:
 MULLION SIZE WAS NOT SPECIFIED.
  
 7- ENGINEER OF RECORD TO APPROVE IN WRITING ABOVE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 8- SOUTH AND NORTH WALL SECTIONS:
 (A) CLARIFY RSP6 SPECIFIED ON THE METAL CONNECTOR
 SCHEDULE AND SOUTH WALL SECTION. THIS CONNECTOR DOESN'T
 EXIST IN THE SIMPSON CATALOG. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 (B) INFORMATION SHOWN AT THE ROOF JOIST SECTION IS NOT
 LEGIBLE. REVISE AS REQUIRED. SEC. 107.2.1.4 CITY
 AMENDMENTS.
  
 NEW COMMENTS:
 9- CLARIFY SECOND NOTE SHOWN ON THE TOP LEFT CORNER OF
 SHEET "1". CLARIFY WHY ARE THE DOORS RATED FOR 140 MPH
 WIND LOAD?. SEE DESIGN STANDARDS ON SAME DRAWING AND
 REVISE AS REQUIRED. ALSO, CLARIFY WHAT IS "(AS PER
 ASD)"?. SEC. 107.2.1 CITY AMENDMENTS.
  
 10- CLARIFY STRUCTURAL NOTES BELOW THE "METAL CONNECTOR
 SCHEDULE". TYPICALLY, SPECIFICATIONS FOR THE ATTACHMENT
 OF DOORS AND WINDOWS TO THE SUBSTRATE ARE INCLUDED IN
 THE PRODUCT APPROVALS. WHAT ARE THESE NOTES FOR?. IS
 THE ENGINEER OF RECORD CHANGING THE PRODUCT APPROVAL
 SPECIFICATIONS? IF SO, THEN COMPLETE ENGINEERING
 ANALYSIS IS REQUIRED. SEC. R301.1 FBC-RESIDENTIAL.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]