| Plan Review Notes For Permit 16100853 |
| Permit Number |
16100853 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-31 17:25:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE SUBMITTED APPLICATION AND DRAWINGS INDICATE THAT | | | ALL SIDEWALL HEADS WERE CHANGED TO PENDANTS. | | | | | | HOW MANY SIDEWALL HEADS WERE REPLACED? | | | | | | WHAT WERE THE SPECIFIC LOCATIONS? | | | | | | 2) THESE MODIFICATIONS ADD AN INCREASED DEMAND ON THE | | | PREVIOUSLY DESIGNED AND APPROVED SYSTEM. | | | | | | 3) NEW BRANCH LINES HAVE BEEN ADDED AND ARE MORE THAN | | | RELOCATED DROPS. | | | | | | HOW WILL THE NEW INSTALLTION BE TESTED? | | | | | | CAN THE FLOOR OR SPACE BE ISOLATED ? | | | | | | 4) THESE MODIFICATIONS MAY NOT BE IN THE SCOPE AND/OR | | | APPROVAL OF THE ENGINEER OF RECORD DESIGN CRITERIA. | | | | | | 5) PROVIDE RECALCULATED HYDRALIC CALCULATIONS SHOWING | | | APPICABLE DEMAND REQUIRMENTS. | | | | | | 6) PROVIDE APPROVAL AND/OR REVIEW FROM ENGEER OF | | | RECORD. | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|