| Plan Review Notes For Permit 16100844 |
| Permit Number |
16100844 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-31 11:52:49 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. PLEASE SHOW JACUZZI TO BE PROTECTED BY GFCI BREAKER | | | TO BE READILY ACCESSIBLE. A NOTE WILL SUFFICE. | | | 2. PROVIDE A NOTE TO INDICATE REQUIRED TAMPER RESISTANT | | | RECEPTACLE. FBC RES E4002.14 | | | 3. PROVIDE A NOTE TO PROVIDE AFCI PROTECTION PER FBC | | | RES E3902.12 | | | 4. PROVIDE THE EXISTING PANEL SCHEDULE REFLECTING NEW | | | JACUZZI AND WATER VALVE LOADS. FBC 107.3.5 | | | 5. CLARIFY IF THERE ARE EXISTING SMOKE DETECTORS IN | | | UNIT IF NOT SHOW AND PROVIDE ON DRAWINGS. FBC RES 315 | | | 6. PROVIDE SPEC SHEETS FOR THE NEW 120V ELECTRONIC | | | SHOWER CONTROL VALVE. | | | 7. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|